FEXC_SEL
Parameter of SETTINGS-function block.
Selection for the type of the field exciter or the type of acknowledgement signal from old
field exciters:
0 = NO FIELD EXCITER
1 = DIODE FIELD EXC.
2 = FEX2 OR FEX3
3 = FEX3 FOR MOTOR2
4 = FEX2/3 + MOT2=FEX3
5 = FIELD ACK VIA DI
6 = FIELD ACK VIA AI
505
FB_P: E2
SC: -
PHASE_SEQ_CW
Parameter of SETTINGS-function block.
The phase order of converter supply voltage. If measured phase order does not match
with this parameter, fault 38 "Phase sequence fault" is generated.
1 = R-T-S
2 = R-S-T
506
FB_P: E2
SC: -
U_SUPPLY
Parameter of SETTINGS-function block
Nominal value of converter supply voltage. (higher HL in S21.232)
507
FB_P: I2
SC: 1
U_NET_MIN1
Parameter of CONVERTER_PROTECTION-function block.
Upper limit for supply undervoltage monitoring in %. If supply voltage falls below this limit,
controllers are blocked. Undervoltage trip is generated if network voltage does not return
to a higher value than U_NET_MIN1 during time defined by PWR_DOWN_TIME.
508
FB_P: I2
SC: 1
U_NET_MIN2
Parameter of CONVERTER_PROTECTION-function block.
Lower limit for supply undervoltage monitoring in %. If supply voltage falls below this limit,
the drive will trip immediately.
509
FB_P: I2
SC: 1
PWR_DOWN_TIME
Parameter of CONVERTER_PROTECTION-function block.
During this time the supply voltage must return to a value higher than U_NET_MIN1.
Otherwise an undervoltage trip will be generated.
510
FB_P: I2
SC: 1
ARM_OVERVOLT_LEV
Parameter of CONVERTER_PROTECTION-function block.
Armature overvoltage tripping level in % of nominal voltage of motor.
511
FB_P: I2
SC: 1
ARM_OVERCURR_LEV
Parameter of CONVERTER_PROTECTION-function block.
Armature overcurrent tripping level in % of converter nominal current.
512
FB_P: I2
SC: 1
HW: only one field exciter (see Technical Data) as Node 1;
SW: MOTOR1_FIELD (10ms update time)
HW: only one field exciter (no SDCS-FEX-2) as Node 2;
SW: MOTOR2_FIELD (100ms update time)
HW: possibility of 2 and 3; SW: MOTOR1 + 2_FIELD
SW: MOTOR1_FIELD
SW: MOTOR1_FIELD
HL: 6
LL: 0
HL: 2
LL: 1
HL: 1400
LL: 0
HL: 130
LL: 0
HL: 130
LL: 0
HL: 5000
LL: 0
HL: 150
LL: 20
HL: 230
LL: 20
DCS500 Pin and Parameter list
( S2/16 )
D: 0
U: -
( S2/16 )
D: 2
U: -
(S2/16 | mod in S21.232)
D: 0
U: V
( S9/16 )
D: 80
U: %
( S9/16 )
D: 60
U: %
( S9/16 )
D: 5000
U: ms
( S9/16 )
D: 110
U: %
( S9/16 )
D: 230
U: %
A 19