NOTE
The UPS is to be installed in a controlled environment.
Improper storage and installation environment may deteriorate
insulation, shorten component life and cause malfunctions.
Keep the installation environment per standard described as follows:
TABLE 1.1
UPS Installation Environment
No.
Item
1
Installation
Indoors
location
2
Ambient
Minimum temperature: 32 F(0 C), Maximum temperature: 104 F(40 C) The
temperature
average temperature over any 24-hour period must be in the range 41 F (5 C)
to 95 F(35 C).
3
Relative humidity The relative humidity must be held between 5 and 95%. There must be no
condensation due to temperature changes.
4
Altitude
This equipment must not be applied at altitude that exceeds 2250m(7400ft)
above seal level.
5
Dust
Dust in the room where the UPS is installed must not exceed normal
atmospheric dust levels. In particular, that dust should not include iron particles,
oils or fats, or organic materials such as silicone.
6
Inflammable gas
There should be no inflammable/explosive gas.
Hydrogen sulfate (H
following
Sulfurous acid gas (SO
IEC654-4
Chlorine gas (Cl
Part 4
Ammonia gas (NH
Nitrous oxides (NO
Ozone (O
4
WARNING 3
4
Environment standard
S)
2
)
2
)
2
)
3
)
x
)
3
No more than 0.003 PPM
No more than 0.01 PPM
No more than 0.002 PPM
No more than 1 PPM
No more than 0.05 PPM
No more than 0.002 PPM
G9000 Installation and Operation Manual