Table 2-1 Ups Installation Environment - Toshiba G9000 SERIES Installation And Operation Manual

480/480 v 100/160/225/300/500/750 kva
Hide thumbs Also See for G9000 SERIES:
Table of Contents

Advertisement

!
NOTE
The UPS is to be installed in a controlled environment.
Improper storage and installation environment may deteriorate insulation, shorten component
life and cause malfunctions.
Keep the installation environment per standard described as follows:
No.
Item
1
Installation
Indoors
location
Minimum temperature: 32 °F(0 °C), Maximum temperature: 104 °F(40 °C) The
2
Ambient
average temperature over any 24-hour period must be in the range 41 °F (5 °C)
temperature
to 95 °F(35 °C).
3
Relative humidity The relative humidity must be held between 5 and 95%. There must be no
condensation due to temperature changes.
4
Altitude
This equipment must not be applied at altitude that exceeds 2250m (7380ft)
above sea level.
5
Dust
Dust in the room where the UPS is installed must not exceed normal
atmospheric dust levels. In particular, that dust should not include iron particles,
oils or fats, or organic materials such as silicone.
6
Inflammable gas
There should be no inflammable/explosive gas.
Hydrogen sulfide (H
following
Sulfurous acid gas (SO
IEC654-4
Chlorine gas (Cl
Part 4
Ammonia gas (NH
Nitrous oxides (NO
Ozone (O
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
WARNING 3

Table 2-1 UPS Installation Environment

Environment standard
S)
2
)
2
)
2
)
3
)
x
)
3
No more than 0.003 PPM
No more than 0.01 PPM
No more than 0.002 PPM
No more than 1 PPM
No more than 0.05 PPM
No more than 0.002 PPM