Toshiba TOSNIC-7000S Instruction Manual

Toshiba uninterruptible power system instruction manual

Advertisement

Quick Links

Uninterruptible Power System (UPS)
TOSNIC-7000S
Instruction Manual (OPERATION)
REQUIREMENT
• This manual should be delivered to the persons who
will ultimately use and maintain the UPS.
• Read this manual carefully before operating the UPS.
• Store the manual in a safe place so it can be referred
to when needed.
July 1999
6 F 3 H 1 0 0 1
©
ALL Rights Reserved.

Advertisement

Table of Contents
loading

Summary of Contents for Toshiba TOSNIC-7000S

  • Page 1 Uninterruptible Power System (UPS) TOSNIC-7000S Instruction Manual (OPERATION) REQUIREMENT • This manual should be delivered to the persons who will ultimately use and maintain the UPS. • Read this manual carefully before operating the UPS. • Store the manual in a safe place so it can be referred to when needed.
  • Page 2 Every effort has been made to ensure that the information in this manual is correct and accurate in all respects. If you note inconsistencies or omissions, or if you have any questions, please contact the Toshiba Service Center. Molded Case Circuit Breaker Air Circuit Breaker A parallel UPS system in which there is a battery for each UPS in the system.
  • Page 3: Introduction

    1. Introduction This manual is designed to ensure the safe and correct operation of the TOSNIC-7000S Uninterruptible Power System (hereafter referred to as "UPS unit"). Please read the "Safety Precautions" and "Operation" sections of this manual carefully before use and make sure you have a thorough understanding of the information in these two sections.
  • Page 4 Special considerations (*) are required when using equipment that affects the lives and safety of human beings (**) or has a critical effect on maintaining public services (***). Be sure to contact Toshiba in such cases. The use of such equipment without special consideration may result in serious accidents.
  • Page 5 52R and 72B. Continued use may result in fire. Contact the Toshiba Service Center. Contact the Toshiba Service Center in the event of malfunction or failure. This unit should be repaired only by authorized Toshiba service personnel. Servicing by untrained personnel may increase the scale of the failure or result in electric shock or injury.
  • Page 6 Safety Precautions (continued) Do not open the rear door. The parts inside carry high voltage. Touching them may result in electric shock, burns or failure. Operators should be qualified* personnel. Operation of the UPS by unqualified or untrained personnel may result in electric shock, injury or failure. In accordance with customer stipulations Make sure the air vents on the front and top of the unit are not blocked.
  • Page 7 Safety Precautions (continued) Checking warning labels (1) The locations of the warning labels on the UPS are shown in Figure 2.1. Check to make sure that these warning labels are in place. Note that the placement and content of the warning labels may differ depending on the capacity of the UPS.
  • Page 8: Handling Precautions

    Be sure to have periodic maintenance work and inspections done by Toshiba service and maintenance personnel. For more information on servicing programs and fee options, contact the Toshiba Service Center.
  • Page 9 Handling Precautions (continued) Do not turn the circuit breakers ON when control power source switch (8A) is OFF. This may result in failure. Certain units also have a control power source switch (8D). This switch has the same functions as the switch 8A. Do not turn the control power source switch (8A) to the OFF position when the circuit breakers are ON.
  • Page 10 Handling Precautions (continued) When the unit has stopped due to failure, be sure to remove the memory card before resetting the LCD Failure Error screen on the panel. Resetting (restarting) the UPS without removing the memory card will delete the data needed to determine the cause of the failure. Do not leave the unit for long periods of time (1 week) with control power source switch (8A) in the OFF position.
  • Page 11: Table Of Contents

    4. Contents 1. Introduction ····························································································································2 2. Safety Precautions ·················································································································2 3. Handling Precautions ············································································································7 4. Contents································································································································10 5. Appearance···························································································································11 6. Controls and Circuit Configuration·····················································································12 6.1 Panel Controls ·················································································································12 6.2 Circuit Configuration········································································································13 6.3 Panel Controls ·················································································································14 6.3.1 Panel Key-switch·································································································15 6.3.2 Panel Keys ··········································································································15 7.
  • Page 12: Appearance

    5. Appearance Only open the front panel when performing necessary operations.* WARNIN Do not open the rear door. Make sure the air vents on the front and top of the unit are not blocked. CAUTION Example: 300 kVA Front panel handle (includes a lock) Front air vent This is an example of the appearance of a standard configuration unit (300 kVA) UPS.
  • Page 13: Controls And Circuit Configuration

    Example: 300 kVA The figure above is only an example; the layout may be different depending on capacity and system configuration. Continued use may result in fire. Contact the Toshiba Service Center . This may result in failure. This may result in failure.
  • Page 14: Circuit Configuration

    Device Name / Function Main circuit AC input circuit breaker When the AC input is normal, power is supplied to the UPS through this circuit breaker. Main circuit DC input circuit breaker When AC input has been cut off, power is supplied from the battery to the UPS through this circuit breaker.
  • Page 15: Panel Controls

    Panel Controls When the unit has stopped due to failure, be sure to remove the memory card before resetting the LCD Failure Error screen on the panel, so you can give it to the service person. Resetting (restarting) the UPS without removing the memory card will delete the data needed to determine the cause of the failure.
  • Page 16: Panel Key-Switch

    6.3.1 Panel Key-switch Table 6.2 shows the function of the key-switch on the graphic display panel. Name Function OPERATION Setting this key-switch to the "OPERATION" LOCK side enables operation using the buttons on the panel; setting it to the "OPERATION INHIBITED"...
  • Page 17 Table 6.3 Key Functions (For HS or AHH individual battery systems) (continued) Name Function FLOAT / EQUAL** Changes the battery charging mode. SCROLL UP These keys switch the screen displayed on the LCD. SCROLL DOWN RESET Resets the Failure Data screen and Warning Data screen shown on the LCD.
  • Page 18: Panels

    7. Panels 7.1 Graphic Display Panel Figure 7.1.1 and 7.1.2 and Table 7.1 show the locations and functions of the controls on the graphic display panel. ~ AC INPUT BATTERIES ~ BYPASS INPUT This will be the "PROTECTION" LED for MSE individual battery systems. ** This will be the "FLOAT"...
  • Page 19 UPS SUPPLY ~ ~ AC INPUT CONVERTER FLOAT CHARGE BATTERIES DISCHARGE ~ BYPASS INPUT OPERATION OPERATION INHIBITED Figure 7.1.2 Graphic Display Panel Control (Graphic Display Panel of the type without the equalized charge mode and the protection charge mode). SCROLL WARNING FAULT ~...
  • Page 20: Lcd Display

    Table 7.1 Display Panel Functions (For HS or AHH individual battery systems) Name LCD INDICATOR UPS SUPPLY LED WARNING LED FAULT LED AC INPUT LED CONVERTER LED INVERTER LED AC OUTPUT LED BATTERIES LED FLOATING CHARGE LED** EQUAL CHARGE LED* DISCHARGE LED BYPASS INPUT LED UPS LED...
  • Page 21: Normal Display Screen

    7.2 LCD Display The LCD Display screens consist of the following screens. (1) Normal Display screen ... Initial display, operation guidance, and measurement (2) Failure Data Display screen ... Displays detailed data when a failure occurs. (3) Warning Data Display screen ... Displays detailed data when a warning occurs. The operator can switch between these screens by pressing the scroll keys.
  • Page 22 7.2.1 Normal Display Screen The Normal Display screen indicates the operational status of the UPS and provides a total of nine screens: one Operation Guidance Display screen and eight Measurement Value Display screens. Table 7.2 presents examples of these screens. LCD Screen Help screen (Example 1) Operation status...
  • Page 23 Table 7.2 Measurement screen (Example) Output frequency O/P FREQUENCY FREQ. 60.0[Hz] Measurement screen (Example) AC input AC INPUT AC I/P-V 200[V] FREQ. 60.0[Hz] Measurement screen (Example) Bypass input BYPASS INPUT BYP I/P-V 200[V] FREQ. 60.0[Hz] Measurement screen (Example) DC value DC INPUT DC-V 401[V]...
  • Page 24: Failure Display Screen

    7.2.2 Failure Display Screen The Failure Display screen indicates the presence or absence of failure data and displays that data if present. LCD Screen Presence or absence of failure data FAULT NO FAULT INFORMATION Failure data FAULT 1 52R TRIP 98-09-09 08:05:30 ↓ANOTHER ITEM If there is failure data, that data will remain in the system, even after the actual cause of the...
  • Page 25: Lcd Screen Switching

    7.2.4 LCD Screen Switching The △ and ▽ scroll buttons on the front of the panel are used to switch the screen displayed on the LCD. See figure 6.3.1 for the location of the △ and ▽ scroll buttons. Symbol Name SCROLL ▲...
  • Page 26: Operation

    8. Operation Operators should be qualified* personnel. CAUTION Make sure you understand the meaning of the warning labels on the equipment, and follow the precautions indicated. This section will describe the basic procedures used to operate the UPS. Operate the unit within the ambient conditions noted in the specifications.
  • Page 27: Types Of Operation

    8.1 Types of Operation This section summarizes the types of operations covered in this manual and their objectives. Refer to the attached operating procedures document for specific details on the operating procedures. Operation Startup Switch Power Supply Switches between UPS power supply and Stop Complete shutdown Charge...
  • Page 28: Procedures

    8.3 Procedures 8.3.1 Startup Table 8.1 shows the procedure used to start up the UPS. LED status Step Procedure Turn on the control power supply switch (8A) on the panel. Turn on the bypass AC input 52C and the AC output 52L circuit breakers.
  • Page 29 Table 8.1 Step Procedure LCD/LED Status (After Execution) Wait several seconds.** When the message appears, turn on the main circuit AC input circuit breaker (52R). Wait several seconds. ** Do not turn on circuit breaker 52R until the following message appears on the display: "...
  • Page 30 Table 8.1 Step Procedure LCD/LED Status (After Execution) Hold down the "RUN" key ( in Figure 6.3.1 on page 14) for at least 0.5 second. Wait several seconds for the startup process to finish. When the message appears, turn on the main circuit DC input circuit breaker (72B).
  • Page 31 UPS power supply). →This completes the UPS staartup operation. *If for some reason the AC switch dose not function, contact the Toshiba Service Center. Do not manually operate the solenoid contactor (which is part of AC switch). Startup Procedures (continued) UPS SUPPLY...
  • Page 32: Switch Power Supply (Ups → Bypass)

    8.3.2 Switch Power Supply (UPS → Bypass) Table 8.2 shows the procedure used to switch between UPS power supply and bypass power supply. Table 8.2 Step Procedure Check to make sure power is being supplied to the UPS. Hold down the "BYPASS"...
  • Page 33 6 F 3 H 1 0 0 1 Toshiba Service Center. Do not manually operate the solenoid contactor (which is part of AC switch). - 32 -...
  • Page 34: Stop

    8.3.3 Stop Table 8.3 shows the procedure used to stop the UPS. Step Procedure Change to bypass supply as described in Table 8.2 on page 31. Hold down the "STOP" key ( in Figure 6.3.1 on page 14) for at least 0.5 second.
  • Page 35 Table 8.2 Step Procedure LCD/LED Status (After Execution) Turn off the main DC input circuit breaker(72B). → This complete UPS shutdown Stop (continued) BYPASS RESTART : PRESS ‘RUN’ SWITCH SHUTDOWN : MOVE #52R TO ‘OFF’ ~ ~ ~ AC INPUT CONVERTER INVERTER FLOAT CHARGE...
  • Page 36: Complete Shutdown

    8.3.4 Complete Shutdown This section describes the procedure used to turn off the control power source and shut down the UPS completely (to turn everything up to the control power source off). Step Procedure Same as steps 1-4 in Section 8.3.3 "Stop." When the message appears, turn off the main circuit AC input...
  • Page 37 Table 8.4 Step Procedure LCD/LED Status (After Execution) Turn off the precharge circuit switch (6CH). Wait about 20 minutes until the DC capacitor has been discharge.* Using the scroll keys, change the display screen and check to make sure that the DC voltage is 0V (see Section 7.2.4 “LCD Screen Switching”...
  • Page 38: Changing Between Floating Charge And Equalized Charge

    This must be done about once every six months, in spring and autumn if possible. The TOSNIC-7000S UPS is equipped with a function that performs the equalized charging process automatically when restoring the battery charge after a power outage or the like.
  • Page 39 (2) Table 8.5 shows the procedure used to change manually from equalized charge to floating charge. After the charging mode has been changed to equalized charge using the procedure on the previous page, the mode will automatically change back to floating charge after a set period of time has elapsed.
  • Page 40: Changing To Floating Charge Etc. (For Mse Individual Battery)

    8.3.6 Changing to Floating Charge etc. (for MSE individual battery) Table 8.7 shows the procedure used to change manually from protective charge to floating charge. This operation does not apply to shared battery systems. (1) An MSE battery normally operate in floating charge mode. (2) To prevent the battery temperature from rising, the mode changes automatically to protective charge mode when a "BATT FAULT1"...
  • Page 41: Changing The Power Supply To Maintenance Bypass

    8.3.7 Changing the Power Supply to Maintenance Bypass This UPS must be completely shut down when performing maintenance and inspections. In such cases, the power supply to the load will go through the maintenance bypass. Table 8.8 shows the procedure used to change the power supply to this maintenance bypass. Table 8.9 shows how to change the power supply from the maintenance bypass back to the UPS.
  • Page 42 Table 8.9 Changing From Maintenance Bypass to UPS Power Supply Step Procedure LCD/LED Status (After Execution) Same as steps 1-4 in Section 8.3.1 “Startup” Turn OFF maintenance bypass AC circuit breaker 52M. * Same as steps 5-11 in Section 8.3.1 “Startup” →Change to UPS power supply complete.
  • Page 43: Troubleshooting

    9. Troubleshooting When an error occurs on the UPS, error data is displayed on the LCD screen and the waveform is saved. This section will describe the types of errors, the error messages displayed on the LCD screen, the process of saving waveforms and the procedures used to correct the errors.
  • Page 44: Lcd Failure Displays

    9.2 LCD Failure Displays When a failure occurs, a screen such as that shown in Figure 9.1, and when a warning occurs, a screen such as that shown in Figure 9.2, will be displayed on the LCD. FAULT STOP SERVICEMAN CALL UPS SUPPLY AC-VO AC- I O...
  • Page 45: Warning Data Screen

    9.2.2 Warning Data Screen These screens appear when a warning has occurred. Up to 10 screens can be displayed. Figure 9.4 and Table 9.2 show an example of this type of screen and describe the data shown in the screen. Figure 9.4 Table 9.2 Name...
  • Page 46: Failure Messages

    9.2.3 Failure Messages Figures 9.6 show the locations for failure detection. Tables 9.4 through 9.8 list the failure messages described in Section 9.2.1 "Failure Data Screen". The content and display text for the failure and warning messages in Tables 9.4 through 9.8 have been created based on the standard protective configuration shown in Figures 9.6.UPS units can be shipped with different protective configurations from the standard if this is specified by the customer.
  • Page 47 Item LCD Message Indication 52RT 52R TRIP 72BT 72B TRIP 71BF DC FUSE BLW 86MU MU FAULT1 WDCPU WDCPU 80PS CONT. PS. ERR 80B1 BATT UV EPO SW ON Table 9.5 Warning - 1 (Converter stop/Input power error) Item LCD Message Indication AC I/P UV AC I/P OV...
  • Page 48 Table 9.7 Item LCD Message Indication BYPASS OV BYPASS UV BYPASS ASY Table 9.8 Item LCD Message Indication LOAD LIMIT 51LI O/P OC (PEAK) 72BO 72B MIS OPE. BATT FAULT1 BATT FAULT2 * 80B2 BATT UV (ALM) 76CH BATT OC AC PHASE ERR BYPASS ERR STARTUP ERR...
  • Page 49: Scrolling Through Lcd Screens In The Event Of Failure

    9.2.4 Scrolling Through LCD Screens in the Event of Failure When the unit has stopped due to failure, be sure to remove the memory card before resetting the LCD Failure Error screen on the panel, so you can give it to the service person. Resetting (restarting) the UPS without removing the memory card will delete the data needed to determine the cause of the failure.
  • Page 50 Name Description SCROLL UP Scrolls to the previous screen (see Figure 9.9) SCROLL DOWN Scrolls to the next screen (see Figure 9.9) RESET Deletes the stored waveform and failure and warning data from the memory card. (**) (**) Remarks * See section 7.2.1 (on page 21, Normal Display Screen", for details on the content of the Normal Display screen.) ** i ii , etc.
  • Page 51: Saving Waveforms

    Memory card manual write switch Used to write arbitrary data to the memory card.** Do not remove the memory card when the LED is used when adjusting the UPS and should only be used by a Toshiba serviceman or by maintenance personnel. This switch is not used during normal operation. - 50 - 6 F 3 H 1 0 0 1 is lit.
  • Page 52: Restoring Ups Operation

    Electric shock, injury or failure may result if persons other than specially trained Toshiba technicians attempt to modify or move the unit. Be sure to contact Toshiba if you wish modifications to be made or if you wish to move the unit.
  • Page 53 In the case of other failures as well, restore by doing the following: (1) Check the nature of the failure on the LCD screen. (2) Contact the Toshiba Service Center. (3) Follow the directions given by Service Center personnel. Note: Before removing the memory card, always verify that the memory card write LED shown in figure 9.10 is not lit.

Table of Contents