TABLE 1.6 Rating of Contactors, Breaker and Fuses
NUMBER
CB1
CB3
52C
52S
88RC
Control circuit contactor
Battery disconnect breaker
CB2
User supply
(OPTION)
User supply
(OPTION)
User supply
(OPTION)
FCU, FCV, FCW
FCR, FCS, FCT
FPU, FPV
FNU, FNV
FUA, FUB, FUC
FSU, FSV,
FSW(OPTION)
FZS1, 2, 3
Bypass input ZNR fuse
FBS1, 2, 3
FZR1, 2, 3
FEA, FEB, FEC
G9000 Installation and Operation Manual
APPLICATION
AC input contactor
STS contactor
Inverter output
contactor
Bypass contactor
(Recommended)
AC input breaker
(Recommended)
AC bypass breaker
(Recommended)
AC output breaker
(Recommended)
DC fuse
315A / 690V
DC fuse
200A / 690V
Control power fuse
Bypass input fuse
250A / 690V
Control power fuse
AC input ZNR fuse
Parallel control
circuit fuse
OUTPUT CAPACITY OF EQUIPMENT
80kVA
100kVA
72kW
90kW
135A
135A
80A
80A
135A
135A
135A
135A
20A
20A
225A
300A
125A
150A
125A
150A
125A
150A
315A / 690V
200A / 690V
30A / 600V
30A / 600V
250A / 690V
5A / 500V
5A / 500V
30A / 600V
30A / 600V
5A / 500V
5A / 500V
3A / 600V
3A / 600V
160kVA
225kVA
144kW
202.5kW
200A
285A
135A
150A
200A
285A
200A
285A
20A
20A
400A
600A
250A
350A
250A
350A
250A
350A
200A / 690V
200A / 690V
350A / 690V
350A / 690V
30A / 600V
30A / 600V
200A / 690V
250A / 690V
5A / 500V
5A / 500V
30A / 600V
30A / 600V
5A / 500V
5A / 500V
3A / 600V
3A / 600V
19

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

T90s3s10ks6xsnT90s3s16ks6xsnT90s3s22ks6xsn