Table 2-1 Ups Installation Environment - Toshiba G9000 SERIES Installation And Operation Manual

480/480 v 1000/1330/1500/1660/2000kva
Hide thumbs Also See for G9000 SERIES:
Table of Contents

Advertisement

WARNING
The UPS is to be installed in a controlled environment.
Improper storage and installation environment may deteriorate insulation, shorten
component life and cause malfunctions.
Keep the installation environment per standard described as follows:
No
Item
1
Installation
Location
2
Ambient
temperature
3
Relative humidity
4
Altitude
5
Dust
6
Inflammable gas
following
IEC654-4
Part 4
4
WARNING 3
4
Table 2–1 UPS Installation Environment
Environment standard
Indoors
Minimum temperature: 32F(0C)
Maximum temperature: 104F(40C)
The average temperature over any 24-hour period must be in the range
41 F (5C) to 95F(35C).
The relative humidity must be held between 5 and 95%.
There must be no condensation due to temperature changes.
This equipment is designed to operate without derating at 1980m (6500ft)
above sea level.
Dust in the room where the UPS is installed must not exceed normal
atmospheric dust levels. In particular, that dust should not include iron
particles, oils or fats, or conductive materials such as silicone.
There should be no inflammable/explosive gas.
Hydrogen sulfide (H
S)
2
Sulfurous acid gas (SO
)
2
Chlorine gas (Cl
)
2
Ammonia gas (NH
)
3
Nitrous oxides (NO
)
x
Ozone (O
)
3
G9000 1000-2000kVA Installation and Operation Manual 91469-007
No more than 0.003 PPM
No more than 0.01 PPM
No more than 0.002 PPM
No more than 1 PPM
No more than 0.05 PPM
No more than 0.002 PPM