Table 3.4 Recommended Cable Sizes - Toshiba T90S3S08KS6XSN Manual

Uninterruptible power systems g9000 series 80/100/160/225 kva
Hide thumbs Also See for T90S3S08KS6XSN:
Table of Contents

Advertisement

TABLE 3.4 Recommended Cable Sizes

kVA
Input
Output
Cable
Capacity
Voltage
Voltage
Size
1 AWG –
80kVA
480V
480V
1/0 AWG
2/0 AWG –
100kVA
480V
480V
3/0 AWG
250 MCM –
160kVA
480V
480V
300 MCM
500 MCM
225kVA
480V
480V
2x250 MCM
*1 - The cables must be selected to be equal to the sizes listed in the table.
*2 - Voltage drop across power cables not to exceed 2% of nominal source voltage.
*3 - Allowable ampere-capacities based on 75 C insulated copper conductor at ambient temperature of 40 C.
*4 – All wiring to be in accordance with all applicable national and/or local electrical codes.
G9000 Installation and Operation Manual
Input Side
Output Side
Torque
Cable
in. lbs
Size
1 AWG –
100 - 135
in. lbs
1/0 AWG
2/0 AWG –
100 - 135
in. lbs
3/0 AWG
250 AWG –
100 - 135
in. lbs
300 MCM
100 - 135
500 MCM
in. lbs
2x250 MCM
Bypass Side
Torque
Cable
Torque
in. lbs
Size
in. lbs
1 AWG –
100 - 135
100 - 135
in. lbs
1/0 AWG
in. lbs
2/0 AWG –
100 - 135
100 - 135
in. lbs
3/0 AWG
in. lbs
250 MCM –
100 - 135
100 - 135
in. lbs
300 MCM
in. lbs
100 - 135
500 MCM
100 - 135
in. lbs
2x250 MCM
in. lbs
DC Input Side
Cable
Torque
Size
in. lbs
250 MCM –
100 - 135
300 MCM
in. lbs
350 MCM –
100 - 135
400 MCM
in. lbs
2x350 MCM –
100 - 135
2x400 MCM
in. lbs
3x300 MCM –
100 - 135
3x350 MCM
in. lbs
41

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

T90s3s10ks6xsnT90s3s16ks6xsnT90s3s22ks6xsn