Table 2-1 Ups Installation Environment - Toshiba G9000 Series Installation And Operation Manual

480/480 v 300/500/650/750 kva
Hide thumbs Also See for G9000 Series:
Table of Contents

Advertisement

!
NOTE
The UPS is to be installed in a controlled environment.
Improper storage and installation environment may deteriorate insulation, shorten component life and cause
malfunctions.
Keep the installation environment per standard described as follows:
No.
Item
1
Installation location Indoors
2
Ambient
temperature
3
Relative humidity The relative humidity must be held between 5 and 95%. There must be no
4
Altitude
5
Dust
6
Inflammable gas
following
IEC654-4
Part 4
G9000 Series UPS 300-750kVA Installation and Operation Manual – 61480-017
WARNING 3
Table 2–1 UPS Installation Environment
Minimum temperature: 32 F(0 C), Maximum temperature: 104 F(40 C) The
average temperature over any 24-hour period must be in the range 41 F (5 C)
to 95 F(35 C).
condensation due to temperature changes.
This equipment must not be applied at altitude that exceeds 2250m (7380ft)
above sea level.
Dust in the room where the UPS is installed must not exceed normal atmospheric
dust levels. In particular, that dust should not include iron particles, oils or fats,
or organic materials such as silicone.
There should be no inflammable/explosive gas.
Hydrogen sulfide (H
S)
2
Sulfurous acid gas (SO
2
Chlorine gas (Cl
)
2
Ammonia gas (NH
)
3
Nitrous oxides (NO
)
x
Ozone (O
)
3
Environment standard
No more than 0.003 PPM
)
No more than 0.01 PPM
No more than 0.002 PPM
No more than 1 PPM
No more than 0.05 PPM
No more than 0.002 PPM
5