Table 2-1 Ups Installation Environment - Toshiba G2020 Series Installation And Operation Manual

480/480 v 500kva/750kva
Hide thumbs Also See for G2020 Series:
Table of Contents

Advertisement

WARNING
The UPS is to be installed in a controlled environment.
Improper storage and installation environment may deteriorate insulation, shorten component life and cause
malfunctions.
Keep the installation environment per standard described as follows:
No
Item
Installation
1
Location
2
Ambient
temperature
3
Relative
humidity
4
Altitude
5
Dust
6
Inflammable
gas
following
IEC654-4
Part 4
G2020 Series UPS Installation and Operation Manual – 94861-004
WARNING 3
4

Table 2-1 UPS Installation Environment

Minimum temperature: 32F (0C)
Maximum temperature: 104F (40C)
The average temperature over any 24-hour period must be in the range
The relative humidity must be held between 5 and 95%.
There must be no condensation due to temperature changes.
This equipment is designed to operate without derating at 1980m (6500ft)
Dust in the room where the UPS is installed must not exceed normal
atmospheric dust levels. In particular, that dust should not include iron
particles, oils or fats, or organic materials such as silicone.
There should be no inflammable/explosive gas.
Hydrogen sulfide (H
S)
2
Sulfurous acid gas (SO
2
Chlorine gas (Cl
)
2
Ammonia gas (NH
)
3
Nitrous oxides (NO
)
x
Ozone (O
)
3
Environment standard
Indoors
41F (5C) to 95F (35C).
above sea level.
No more than 0.003 PPM
)
No more than 0.01 PPM
No more than 0.002 PPM
No more than 1 PPM
No more than 0.05 PPM
No more than 0.002 PPM
5