External Signal Terminal Block; Figure 2.10.1 External Signal Terminal Block (Tn2) - Toshiba T90S3S08KS6XSN Manual

Uninterruptible power systems g9000 series 80/100/160/225 kva
Hide thumbs Also See for T90S3S08KS6XSN:
Table of Contents

Advertisement

2.4

EXTERNAL SIGNAL TERMINAL BLOCK

The UPS is equipped with a series of input/output terminals for external annunciation of alarms
and for remote access of certain UPS functions. The layout of terminals is shown in Figure 2.10.1 and
2.10.2 with a functional description of the input/output port presented. OUT1 to OUT8 are user
programmable, but factory default settings are shown in Figure 2.10.1.
Adding same external I/F PCB "IOAU-09", doubling signal outputs is applicable for OUT1 to OUT8.
FIGURE 2.10.1 External Signal Terminal Block (NEC Class2)
TN2
2
4
6
8
10
12
14
16
18
20
UPS
28
1
3
5
7
9
11
13
15
17
19
*1
*1 Relay contactor (52C close): Normal Closed
SUMMARY ALARM
OUT1: LOAD ON BYPASS
OUT2: LOAD ON INVERTER
OUT3:BATTERY OPERATION
OUT4: CONVERTEN OPERATION
OUT5: BATTERY LOW VOLTAGE
OUT6: OVERLOAD
OUT7: SPARE
OUT8: TOTAL ALARM
52C CLOSE
G9000 Installation and Operation Manual