Table 2-1 Ups Installation Environment - Toshiba G9000 SERIES Installation And Operation Manual

480/480 v 1000kva
Hide thumbs Also See for G9000 SERIES:
Table of Contents

Advertisement

No
Item
1
Installation
Location
2
Ambient
temperature
3
Relative
humidity
4
Altitude
5
Dust
6
Inflammable
gas
following
IEC654-4
Part 4
4

Table 2-1 UPS Installation Environment

Environment standard
Indoors
Minimum temperature: 32°F(0°C), Maximum temperature: 104°F(40°C)
The average temperature over any 24-hour period must be in the range
41° F (5°C) to 95°F(35°C).
The relative humidity must be held between 5 and 95%. There must be
no condensation due to temperature changes.
This equipment must not be applied at altitude that exceeds
1980m(6500ft) above seal level.
Dust in the room where the UPS is installed must not exceed normal
atmospheric dust levels. In particular, that dust shoud not include iron
particles, oils or fats, or organic materials such as silicone.
There should be no inflammable/explosive gas.
Hydrogen sulfide (H
S)
2
Sulfurous acid gas (SO
)
2
Chlorine gas (Cl
)
2
Ammonia gas (NH
)
3
Nitrous oxides (NO
)
x
Ozone (O
)
3
G9000 1000kVA Installation and Operation Manual – 91469-004
No more than 0.003 PPM
No more than 0.01 PPM
No more than 0.002 PPM
No more than 1 PPM
No more than 0.05 PPM
No more than 0.002 PPM

Advertisement

Table of Contents
loading

Table of Contents