Figure 1.2 Single Line Diagram - Bypass Operation - Toshiba T90S3S08KS6XSN Manual

Uninterruptible power systems g9000 series 80/100/160/225 kva
Hide thumbs Also See for T90S3S08KS6XSN:
Table of Contents

Advertisement

In the event of a UPS module failure during Parallel Operation, the critical load power will be
continually supplied and shared by all other UPS.
!
The Bypass Input breaker and cables are to be supplied and installed by the user or
the constructor. (See WARNING 4 on page 1-4)
NOTE
B) Bypass Operation: Load Power supplied through UPS internal static bypass line.
FIGURE 1.2
CB
Bypass
input
User supplied
MCCB
CB
AC input
User supplied
MCCB
Figure 1.2 shows the Internal Bypass line is a Hard-wired line through 52S which supplies the
critical load with unconditioned bypass input power. Upon switching to the Internal Bypass line, the
Static Transfer Switch line through CB3 (herein after STS contactor CB3) supplies the power
immediately, and then the Internal Bypass line through 52S supplies the power. In the event of a
switching to the Bypass line, the power to the critical load will be uninterrupted. The purpose of this
Internal Bypass line is to route power to the critical load while the UPS module is de-energized
(converter and inverter), and during Start-up before the system is fully operational.
Each UPS internal static bypass line will equally share the power supplied to the critical load
whenever the system is in the Parallel Operation.
G9000 Installation and Operation Manual
Single Line Diagram - Bypass Operation: Load fed through static bypass
line.
UPS Module
CONVERTER
/ CHARGER
CB1
Battery Cabinet
CB2
External
BATTERY
52S
Static Transfer
Switch
CB3
INVERTER
52C
Power Flow
Not in Use
Output
9