Operation Overview; Figure 1.1 Single Line Diagram - Normal Operation - Toshiba T90S3S08KS6XSN Manual

Uninterruptible power systems g9000 series 80/100/160/225 kva
Hide thumbs Also See for T90S3S08KS6XSN:
Table of Contents

Advertisement

1.4

OPERATION OVERVIEW

The UPS provides two power paths between the utility source and the critical load.
Figure 1.1 shows the path for normal operation, with the load powered by the inverter.
Figure 1.2 shows the path for bypass operation, with the load supplied through the static
bypass line.
A)
Normal operation: Load power supplied by each system UPS inverter.
FIGURE 1.1 Single Line Diagram - Normal Operation: Load powered by UPS inverter
CB
Bypass
input
User supplied
MCCB
CB
AC input
User Supplied
MCCB
During normal operation, the path through the UPS inverter is used to power the load.
In Figure 1.1 input AC power is converted to DC by the Converter. DC power is utilized to charge
the UPS battery and to provide power to the Inverter. The Inverter converts the DC power to clean AC
power to supply the critical load.
The conversion - inversion process eliminates any voltage transients or fluctuations existing in the
input power before it reaches the critical load.
The power drawn by the critical load is equally shared between all UPS systems when multiple
UPSs are in Parallel Operation. (Refer to Figure 3.4 that shows a sample of Parallel Operation System
Configuration.)
8
UPS Module
CONVERTER
/ CHARGER
CB1
Battery Cabinet
CB2
External
BATTERY
52S
Static Transfer
Switch
CB3
INVERTER
52C
Power Flow
Not in Use
G9000 Installation and Operation Manual
Output

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

T90s3s10ks6xsnT90s3s16ks6xsnT90s3s22ks6xsn

Table of Contents