Programming
Pressing 1 for Type while viewing the Relay Screen will cause the following screens to be dis-
played:
While viewing the selected screen, press the number corresponding to the desired relay type to pro-
gram the main circuit board relay. The choice will be stored in memory and the display will return
to the Relay Type Screen which will show the programmed type choice. Press the Escape key to
return to the Relays Selection Screen and repeat the preceding procedure for the remaining relays.
Note the following:
1.
2.

Canadian Option

SYSTEM SETUP
1=CANADIAN OPT. OFF
Pressing 1 while viewing System Setup Screen #3 will configure the FACP to comply with Cana-
2=WATERFLOW SIL. NO
3=MNS OVERRIDE
NO
dian requirements. The display will change to Canadian Opt. On. Each press of the 1 key will
System Setup Screen #3
cause the display to toggle between Canadian Opt. On and Canadian Opt. Off.:
Important! For Canadian Applications, this option must be set to ON prior to any other panel pro-
gramming.
The Canadian Options configures the FACP with the following as required by Canada:
100
RELAY
1=ALARM
2=SUPERVISORY
3=SUPERVISORY AR
Relay Screen #1
RELAY
1=PROCESS MON AR
2=AC LOSS
3=HAZARD
Relay Screen #3
AR (AutoResettable) in SUPERVISORY AR and PROCESS MON AR means that a relay with
the Supervisory and/or Process Monitor type code, when activated, will automatically reset
when the corresponding condition is cleared.
A relay programmed with the Silenceable Alarm type will activate upon any alarm and
deactivate when the FACP Alarm Silenced LED is illuminated.
The following monitor module type codes are not available:
• monitor
• non-latching supervisory
• non-latching drill
• non-latching process monitor
• process monitor
• hazard
• tornado
• medical alert
The auto-silence timer is fixed at 20 minutes and cannot be changed.
Addressable ionization smoke detector sensitivity is automatically monitored using Canadian
specifications.
1=TROUBLE
2=COMM FAIL
3=PROCESS MON
1=MEDICAL
2=SILENCEABLE ALARM
SYSTEM SETUP
1=CANADIAN OPT.
OFF
2=WATERFLOW SIL.
NO
3=MNS OVERRIDE
NO
MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Master Programming Level
RELAY
Relay Screen #2
RELAY
Relay Screen #4