SYSTEM SETUP
1=CANADIAN OPT. OFF
2=WATERFLOW SIL. NO
System Setup Screen #3
PROGRAMMING
1=LOOP SETUP
2=SYSTEM SETUP

3=VERIFY LOOP

Programming Screen #2
MS-9200UDLS PN 52750:E1

3.6.5.7 Canadian Option

Pressing 1 while viewing System Setup Screen #3 will allow the programmer to
configure the system to automatically monitor addressable ionization smoke
detector sensitivity using Canadian specifications. The display will change to
Canadian Opt. On. Each press of the 1 key will cause the display to toggle between
Canadian Opt. On and Canadian Opt. Off.:
1=CANADIAN OPT.
2=WATERFLOW SIL.

3.6.5.8 Waterflow Silenceable

Pressing 2 while viewing System Setup Screen #3 will allow the programmer to
configure the system for silenceable on nonsilenceable waterflow circuits. Each
press of the 2 key will toggle the display between Waterflow Sil. No and Waterflow
Sil. Yes. When Waterflow Sil. No is selected, all output devices associated with a
waterflow type input device, will be nonsilenceable. When Waterflow Sil. Yes is
selected, all output devices associated with a waterflow type input device, will be
silenceable.
3.6.6 Verify Loop
Pressing 3 while viewing Programming Screen #2, will select the Verify Loop option.
During loop verification, the FACP polls each device on the SLC to determine if the
device is communicating and whether or not it responds with the proper type
identification. The following screen will be displayed while verification is in progress:
VERIFYING LOOPS
Verification Progress Screen
When Loop verification has been completed, the display will indicate that the system is
OK or, if problems have been detected, any device type programming errors. Use the
up and down arrow keys to view all detected errors.
01/27/09
SYSTEM SETUP
Relays Selection Screen
PLEASE WAIT
Programming
OFF
NO