2: 4Xtmf, 4Xlmf And 4Xzmf Option Modules (Ms-4 Only) - Fire-Lite MS-2 User Manual

Fire alarm control panel
Hide thumbs Also See for MS-2:
Table of Contents

Advertisement

,QVWDOODWLRQ RI 2SWLRQDO 0RGXOHV
+
-
+
-
B+ B-
Nonreset Reset
NAC 1
J9
J7
HOT NEUT EARTH
Figure 2.12 4X Option Module Connection to MS-4
0606 31 % 
2.6.2 4XTMF, 4XLMF and 4XZMF Option Modules (MS-4 only)
The 4XLMF LED Interface Module can only be plugged into connectors J3 and J5 on
the MS-4 main circuit board. The 4XTMF and 4XZMF modules can be plugged into
connectors J3 and J5 or J4 and J6 on the MS-4 main circuit board. A combination of
any two of the three modules can be installed. The following steps must be followed
when installing each of these modules:
1. Remove all power (AC and DC) from the FACP before installing the modules
2. Cut jumper JP1 (for connectors J3 and J5) and/or JP2 (for connectors J4 and J6)
on the main circuit board to allow the control panel to supervise the placement of
any installed option module
3. Install the two supplied metal standoffs in the locations indicated. These
standoffs provide the required earth ground protection
4. Carefully plug the connectors on the option module into connectors J3 and J5 or
J4 and J6 on the FACP main circuit board, being careful not to bend any pins
5. Secure the option module to the standoff on the main circuit board with the
supplied screws
6. When the installation has been completed, connect the wiring to the modules as
indicated in the following sections
7. Test system for proper operation
B+
B-
B+
B-
B+
B-
B+
B+
B-
ZONE 1 ZONE 2
ZONE 3 ZONE 4
NAC 2
CLASS A
CONVERTER
ZONE 1
FIRE ALARM
SUPERVISORY
TROUBLE
MAINTENANCE
ZONE 2
FIRE ALARM
SUPERVISORY
TROUBLE
MAINTENANCE
ZONE 3
FIRE ALARM
SUPERVISORY
TROUBLE
MAINTENANCE
ZONE 4
FIRE ALARM
SUPERVISORY
TROUBLE
MAINTENANCE
NAC
ZONE
NAC
POWER
AC
SYSTEM
DISABLE
DISABLE
FAULT
TROUBLE
POWER
TROUBLE
ALARM
ACK
RESET
SILENCE
ZONE
ENABLE/DISABLE
1
3
2
TB8
EARTH BATT CHG
J8
BATTERY
JP2 Jumper
Cut to install module on J4 & J6
B-
C
NC NO
C TRBL NORM
C
NC NO
ALARM
SUPV
TROUBLE
J1
J3
J5
ALARM
WALK
SILENCE
TEST
WALK
TEST
4
J4
J6
JP1
JP2
SW1
SW2 SW3
,QVWDOODWLRQ
JP3
Standoffs
J3
(when using
J3 & J5
J5
Standoffs
(when using
J4
J4 & J6
J6
JP1 Jumper
Cut to install
module on J3 & J5