Getting Started - Fire-Lite MS-9600LS Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

Product Description
ACM-32A - Annunciator Control Module annunciates 32 alarm zones with 32 red LEDs. In
addition, it has a System Trouble LED, an On Line/Power LED and a local piezo sounder. It
also has a switch for local piezo silence. *In Canada, this module must be used to annunciate
the fire alarm input points/zones only.
AEM-32AF - Annunciator Expander Module annunciates 32 alarm zones with 32 red LEDs.
*In Canada, this module must be used to annunciate the fire alarm input points/zones only.
LCD-80F Remote Fire Annunciator
The LCD-80F annunciator is an 80-character backlit LCD remote fire annunciator that is capable of
displaying English language text. Tactile switches provide remote system Acknowledge, Silence,
Drill and Reset functions. A keyswitch allows enabling/disabling of the tactile switches. Commu-
nications between the control panel and the annunciator is accomplished over a serial interface
employing the EIA-485 communication standard. Up to 32 LCD-80F annunciators may be con-
nected to the EIA-485 circuit. The annunciators may be powered from the host FACP or a remote
UL listed filtered power supply such as the FCPS Series. For more detailed information, refer to
the LCD-80F manual.
The LCD-80F is not for use in Canadian applications.
LCD-80FC Remote Fire Annunciator (for use in Canadian applications)
The LCD-80FC is identical to the LCD-80F except for the tactile switches and keyswitch. There is
no keyswitch, and tactile switches are provided for local silence and lamp test only. No remote sys-
tem functions can be performed from the LCD-80FC annunciator.
LDM Series Lamp Driver Modules (Graphic Annunciator)
The LDM Series Lamp Driver Modules, which consist of the LDM-32F master and LDM-E32F
expander modules, are used to provide an interface to a custom graphic LED annunciator.

1.9 Getting Started

The following is a brief summary of the minimal steps involved in bringing an MS-9600LS/MS-
9600UDLS on-line:
Install Backbox, Power Supply and Main Circuit Board (refer to "Mounting" on page 26).
Address and Install Intelligent Devices (refer to the SLC Wiring Manual).
Enter Autoprogramming (refer to "Autoprogram" on page 67).
Resolve Programming Conflicts.
Go to Point Program to Enter Specific Data (refer to "Point Program" on page 68). Use the
right and left arrow keys to navigate between devices.
24
MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Getting Started