1.3.1 Current Availability
The following figure illustrates the maximum current that is possible for each panel circuit and the
total current available from the FACP power supply.
TB3
Resettable Special
Application Power
for 4-wire smoke detectors
Resettable Special
Application Power
Power #1
Resettable Special
Application Power
Power #2
NAC 1
Style Y or Z
NAC 3
Style Y only
NAC 2
Style Y or Z
NAC 4
Style Y only
TB4
*The combined output current of all Special Applications Power circuits cannot exceed 1.5 amps in standby. Each
circuit is capable of delivering the full 1.5 amps individually.
Refer to the battery calculations section for additional information.

1.4 Controls and Indicators

LCD Display
The FACP uses an 80-character (4 lines X 20 characters) high
viewing angle LCD display. The display includes a long life
LED backlight that remains illuminated. If AC power is lost and
the system is not in alarm, the LED backlight will turn off to
conserve batteries.
LED Indicators
LED indicators are provided to annunciate the following conditions:
AC Power (green)
Fire Alarm (red)
Supervisory (yellow)
Trouble (yellow)
Maintenance/presignal (yellow)
16
1.5 amps max
per circuit
1.5 amps max
per circuit
1.5 amps max
per circuit
3 amps max
per circuit
3 amps max
per circuit
3 amps max
per circuit
3 amps max
per circuit
Figure 1.1 Current Availability
Standby
1.5 Amps Max*
per panel
SYSTEM ALL NORMAL
MS-9600LS Series Manual — P/N 52646:B8 11/20/2015