Installation
circuit. Do not wire to the corresponding A+ and A- terminals on the CAC-4 module. Note that
Zone 1 IDC on the MS-2 and Zone 2 IDC on the MS-4 can be configured as a combination
waterflow/supervisory circuit as illustrated in the following figure.
Class B (Style B)
IDC - 4.7 K
½ watt ELR
(supervised and
power-limited)
Class A (Style Z) NAC
(supervised and power-limited)
Polarized
Polarized
Strobe
Polarized
Circuit polarities
shown in alarm
condition
Figure 2.11 Wiring NACs and IDCs for Class A Operation
2.6.2 4XTMF, 4XLMF and 4XZMF Option Modules
MS-4: The 4XLMF LED Interface Module can only be plugged into connectors J3 and J5 on the
MS-4 main circuit board. The 4XTMF and 4XZMF modules can be plugged into connectors J3
and J5 or J4 and J6 on the MS-4 main circuit board. A combination of any two of the three
modules can be installed.
MS-2: Only the 4XTMF module can be plugged into connectors J3 & J5 on the MS-2 main circuit
board. (No other option modules can be installed on the MS-2).
26
IMPORTANT! All
devices must be
within 20 feet of the
Class A portion of
resistor
the circuit and
P/N:71252
wiring must be in
conduit.
Smoke
Bell
Pull
Station
Horn
1.2 K
½ watt
Heat
In-Line
resistor
P/N:75579
CAC-4 Class A Converter Module
Class A
(Style D) IDC
Combo Waterflow &
Supervisory
20K, ½ watt ELR
resistor P/N:75477
(Style D) IDC
(supervised and
(supervised and
power-limited)
power-limited)
Tamper
Smoke
Tamper
Pull
Station
Waterflow
Heat
MS-2 & MS-4 Series Manual — P/N 51512:G2 10/18/2011
Installation of Optional Modules
Class A
Dummy load all unused
circuits - 4.7 K
½ watt ELR resistor
(P/N: 71245)
MS-4
Circuit Board