To change the zone type for Z02 to Pull Station, scroll the display until Zone Type Program Screen
#2 is displayed. Press 2 to program zone Z02 as a Pull Station zone. The display will return to the
Zones Installed Screen showing zone Z02 and the Pull Station program type. Repeat the procedure
for each zone to be changed.
IMPORTANT! In Zone Type Program Screen #1, selecting WATERFLOW will assign a Water-
flow silenceable zone type to the selected zone. Any signaling devices programmed to the same
zone can be silenced by pressing the Alarm Silence key or by using the auto-silence feature.
To program a waterflow circuit as nonsilenceable, refer to "System Setup" on page 91.
NOTE: Zone Types are only relevant for Central Station reporting. Changing a zone type will only
change how it is reported to the Central Station.

Zones Available

ZONE SETUP
1=ZONE TYPES
Pressing 2 while viewing Zone Setup Screen #3 will display the following screen:
2=ZONES AVAILABLE

3=ZONE MESSAGE

Zone Setup Screen #3
The display will show all of the zones that are still available for programming. Note that an up
and/or down arrow may appear in the upper right corner of the display, indicating that additional
screens of zone information exists. Press the up or down arrow key to view additional screens.
Zone Message
Pressing 3 while viewing Zone Setup Screen #3 will display the following screen:
Pressing the down arrow key will display additional screens for Zones up to Z99. Press the number
key corresponding to the Zone to be programmed. Screens will be displayed allowing the
programmer to select Audio Messages 1 through 14. When an audio message is selected, the
display will return to the Zone Message screen, showing the message selected for that particular
zone. In the example above, Zone 01 has been programmed for Audio Message 1.
3.6.4 Loop Setup
Loop Setup allows the programmer to configure the SLC Loop(s) for NFPA Style 4, 6 or 7 wiring
PROGRAMMING
1=LOOP SETUP
and to select the protocol for each loop. Pressing 1 while viewing Programming Screen #2 will
2=SYSTEM SETUP
cause the following screen to be displayed:
3=VERIFY LOOPS
Programming Screen #2

Loop Selection

Press 1 while viewing the Loop Selection Screen to configure Loop1 or 2 to configure Loop 2. The
following screens will appear for each loop.
90
ZONES AVAILABLE
01 02 03 04 05 06 07
08 09 10 11 12 13 14
15 16 17 18 19
ZONE MESSAGE
1=Z00
NO MESSAGE
2=Z01
MESSAGE 1
3=Z02
NO MESSAGE
LOOP SETUP
1=LOOP 1
2=LOOP 2
3-PROTOCOL
CLIP
Loop Selection Screen
LOOP # SETUP
1=STYLE
4
Loop Setup Screen