PROGRAMMING
1=LOOP SETUP
Pressing 2 for System Setup, while viewing Programming Screen #2, will cause the following
2=SYSTEM SETUP
3=VERIFY LOOPS
screens to be displayed:
Programming Screen #2
1=TROUBLE REM

2=BANNER

3=TIME-DATE

Trouble Reminder

The Trouble Reminder features causes the control panel piezo to sound a reminder 'beep' for
alarms and troubles, after the panel has been silenced. Refer to "System Setup" on page 91, for a
detailed description of this feature. Pressing 1 while viewing System Setup Screen #1 will cause
the display to toggle to Trouble Rem On, which enables this feature. Each press of the 1 key will
cause the display to toggle between Trouble Rem On and Trouble Rem Off.
Banner
The top line of the display, which appears when the control panel is in normal mode, can be
changed by using the Banner option. Pressing 2 while viewing System Setup Screen #1 will cause
the following to be displayed:
BANNER
1=FACTORY
Pressing 1 while viewing the Banner Screen will select the blank factory default banner setting and
2=USER DEFINED
display the following screen:
Banner Screen
Pressing the Enter key will store this selection in nonvolatile memory and return the display to the
Banner Screen.
Pressing 2 while viewing the Banner Screen will display the following screens :
These screens allow the programmer to enter a two line custom banner. A flashing cursor will
appear in the bottom left corner of each display. A maximum of 20 characters (including spaces)
can be entered into each screen for a total of two lines with 40 characters. After entering up to 20
characters in the first screen, press Enter to view the second screen. Enter up to 20 characters in the
second screen in the same manner or just press Enter if a second banner line is not being entered.
To quickly clear the current banner, press the CLR key.
92
Canadian Option: This option allows the automatic programming of the FACP to Canadian
specifications (refer to "Canadian Option" on page 100).
Important! For Canadian Applications, this option must be set to ON prior to any other panel
programming.
Waterflow Silenceable: This option provides the ability to silence any output circuit activated
by a monitor module programmed as a waterflow type.
MNS Override: This option allows the Mass Notification System to override the FACP's
specified NACs and control modules.
SYSTEM SETUP
OFF
System Setup Screen #1
USER DEFINED BANNER
PRESS ENTER IF OK
User Defined Banner Screen #1
SYSTEM SETUP
1=TIMERS
2=NAC
3=RELAYS
System Setup Screen #2
BANNER
1=FACTORY
2=USER DEFINED
Banner Screen
FACTORY BANNER
Factory Banner Screen
USER BANNER - LINE 2
PRESS ENTER IF OK

User Defined Banner Screen #2
MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Master Programming Level
SYSTEM SETUP
1=CANADIAN OPT.
OFF
2=WATERFLOW SIL. NO
3=MNS OVERRIDE
NO
System Setup Screen #3