3: Rtm-8F Option Module Installation - Fire-Lite MS-9200(C) Instruction Manual

Addressable fire alarm control panel
Hide thumbs Also See for MS-9200(C):
Table of Contents

Advertisement

Optional Modules
2.8.3 RTM-8F Option Module Installation
WARNING! Disconnect all sources of power (AC and DC) before installing or removing any modules or wiring
!
Insert the three supplied nylon standoffs into the holes located on the right-side edge of the MS-9200 main circuit
board. Insert the supplied metal standoff on the lower-right corner. Carefully align the pins of J6 on the main circuit
board with connector J1 on the RTM-8F option board. Press firmly on the RTM-8F until it locks in place on the
standoffs. Be certain to tighten the screw into the metal standoff on the lower-right corner. This is critical to the
RTM-8F transient protection. Affix the terminal identification labels provided with the option module.
RTM-8F Module Installation
FIGURE 2-15:
RTM-8F Option Module
insert here
SUPV
AL ARM
TROUBLE
PC/PRINTER TERM COMM
ACS
SHIELD
SL C
SL C
NO C NO NC C NO NC C
A
B B+ A+ B- A-
OUT+ IN+ O UT- IN-
1 COMM 2
T
T
T
B
B
B
3
7
5
J16
SW2
J6
JP3
JP4
SW1
SW3
Main Circuit Board
Document #51003
Main Circuit Board
Standoffs
Use metal screw and standoff here
T
¾" nylon standoffs
B
6
RTM-8F
¾" aluminum standoff with nut
required for transient protection
Rev.E
01/11/02
P/N 51003:E
33