NAC (Notification Appliance Circuit)

SYSTEM SETUP
1=TIMERS
The options for the NACs on the control panel main circuit board can be set by pressing 2 while
2=NAC
3=RELAYS
viewing System Setup Screen #2. The following screens will be displayed:
System Setup Screen #2
The Notification Appliance Circuits can be configured independently by pressing 1 for NAC 1, 2
for NAC 2, 3 for NAC 3, or 4 for NAC 4.
Note that 3=NAC 3 and 4=NAC 4 will only be displayed if the NACKEY NAC option card is
installed, in JP8 of the main circuit board, for Class B operation.
The following screens will be displayed for either selection:
Pressing 1 while viewing NAC Screen #1 will cause the display to change to Enabled No. This will
prevent the selected main circuit board NAC from activating its devices. Each press of the 1 key
will cause the display to toggle between Enabled Yes and Enabled No.
NAC #
1=ENABLED
The main circuit board NAC type can be programmed by pressing 2 while viewing NAC Screen #1.
2=TYPE
3=SILENCEABLE
The following screen will be displayed. Press the down arrow key to view additional screens:
NAC Screen #1
Select the NAC device type by pressing the number corresponding to the type in the appropriate
screen. When the selection is made, the display will return to NAC Screen #1.
The following table contains NAC type codes and their functions:
96
NAC #
1=ENABLED
2=TYPE
3=SILENCEABLE
NAC Screen #1
NAC #
1=ZONE
00 00 00 00 00
2=SIL INHIBITED
NAC Screen #3
Enabled
Type
NAC Type Code
Bell
Horn
Strobe
Synced Strobe
Strobe Sil Sync
Future Use
Future Use
Future Use
Blank
NACS
1=NAC 1
3=NAC 3
2=NAC 2
4=NAC 4
NAC Selection Screen
YES
1=AUTO SILENCE
BELL
2=CODING
YES
1=SYNC TYPE
2=MNS OVERRIDE
NO
NAC TYPE
1=BELL
2=HORN
3=STROBE
Type Screen #1
Special Function
None
None
None
Synchronized to manufacturer
Same as Synced Strobe but Silence turns off audible & visual devices
None
None
None
None
MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Master Programming Level
NAC #
00
TEMPORAL
NAC Screen #2
NAC #
S
NO
NAC Screen #4