Master Programming Level

Waterflow Silenceable

Pressing 2 while viewing System Setup Screen #3 will allow the programmer to configure the sys-
tem for silenceable on nonsilenceable waterflow circuits. Each press of the 2 key will toggle the
display between Waterflow Sil. No and Waterflow Sil. Yes. When Waterflow Sil. No is selected, all
output devices associated with a waterflow type input device, will be nonsilenceable. When Water-
flow Sil. Yes is selected, all output devices associated with a waterflow type input device, will be
silenceable.

MNS Override

Pressing 3 while viewing System Setup Screen #3 will allow the programmer to configure the
system for use with the Mass Notification System (ECC-50/100 panel). Each press of the 3 key
will toggle the display between MNS Override No and MNS Override Yes. When MNS Override
No is selected, the ECC-50/100 panel does not have permission to override the FACP. When MNS
Override Yes is selected, the ECC-50/100 panel will override the FACP, taking control of its NACs
and control modules during a mass notification event. Refer to the ECC-50/100 Manual for more
information.
3.6.6 Verify Loops
Pressing 3 while viewing Programming Screen #2, will select the Verify Loops option and display
PROGRAMMING
the following screen:
1=LOOP SETUP
2=SYSTEM SETUP
3=VERIFY LOOPS
Programming Screen #2
During loop verification, the FACP polls each device on the selected SLC to determine if the device
is communicating and whether or not it responds with the proper type identification. The program-
mer can choose to verify one or both loops by pressing the number corresponding to the choices
shown above.
When the selection is made, the following screen will be displayed while verification is in progress:
When Loop verification has been completed, the display will indicate that the system is OK or, if
problems have been detected, any device type programming errors. Use the up and down arrow
keys to view all detected errors.
3.6.7 History
The History option allows an authorized user to view or erase events which have occurred in the
PROGRAMMING
control panel. Pressing 1 while viewing Programming Screen #3 will display the History options
1=HISTORY
as shown in the following display:
2=WALKTEST
3=OPTION MODULES
Programming Screen #3
MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
VERIFY LOOPS
1=LOOP 1
2=LOOP 2
3=BOTH LOOPS
Verify Loop Select Screen
VERIFYING LOOPS
PLEASE WAIT
Verification Progress Screen
HISTORY
1=VIEW EVENTS
2=ERASE HISTORY
History Screen