Optional Modules and Devices

ANN-BUS Device Addressing

Each ANN-BUS device requires a unique address (ID Number) in order to communicate with the
FACP. A 5-position DIP switch on each device is used to set this address. The address set for these
devices must also be programmed at the FACP for the specific device (refer to the programming
section titled "ANN-BUS Options" on page 106).
A maximum of 8 devices can be connected to the FACP ANN-BUS communication circuit. Device
addresses do not need to be sequential and can be set to any number between 01 and 08. Note that
00 is not a valid address. The following table shows the DIP switch setting for each address.
NOTE: Address (ID Number) DIP switches on some devices may have more than 5 switch
positions. Unless otherwise specified in the documentation supplied with each device, switch
positions 6 and above must be set to OFF.
ANN-80 Remote Fire Annunciator
Specifications
Operating Voltage Range: 18 VDC to 28 VDC
Current Consumption @ 24 VDC nominal (filtered and nonresettable):
• Normal/Standby (no activity): 37.0 mA
• Trouble: 39.0 mA
• Alarm: 40.0 mA
• AC Fail ( not backlit): 15.0 mA
For use indoors in a dry location
Installation
Ensure that all power (AC and DC) has been removed from the FACP before installing the annunci-
ator.
Opening/Closing Annunciator
The following procedure details the steps used to open the annunciator in order to access the termi-
nal block and DIP switches (refer to Figure 2.21 on page 48):
1.
Turn the key switch to the ON (Unlocked) position by turning the key counter-clockwise.
2.
Push in the snap latch located on the right side of the unit while pulling the cover open.
3.
To close the cover, make certain the key switch is in the ON (Unlocked) position. Swing the
cover closed, snapping it shut.
4.
Turn the key switch to the OFF (Locked) position by turning clockwise and remove the key.
MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
1
Address
Switch 5
not valid
OFF
01
OFF
02
OFF
03
OFF
04
OFF
05
OFF
06
OFF
07
OFF
08
OFF
1 Switch 5 must be set to OFF for ANN-BUS devices to be recognized.
Switch 4
Switch 3
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
ON
ON
OFF
Installation
Switch 2
Switch 1
OFF
OFF
OFF
ON
ON
OFF
ON
ON
OFF
OFF
OFF
ON
ON
OFF
ON
ON
OFF
OFF
47

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ms-9600lseMs-9600udlsMs-9600udlseMs-9600lsc

Table of Contents