15: Print - Fire-Lite MS-9600LS Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

Operating Instructions
4.23.15 Print
To print program data or control panel status, press 3 while viewing Read Status Screen #5. The fol-
READ STATUS
1=SERVICE TERMINAL
lowing screens will be displayed:
2=PRINTER/PC
3=PRINT
Read Status Screen #5
Pressing 1 while viewing Print Screen #1 allows the user to print the History file which will detail
all of the system activities since the file was last cleared from memory.
Pressing 2 while viewing Print Screen #1 allows the user to print the Walktest log which will detail
all of the system activations during walktest since the log was last cleared. Refer to "Walktest" on
page 137 for additional information on the display.
Pressing 3 while viewing Print Screen #1 allows the user to print the detector data for each address-
able smoke detector connected to the system. A printout, similar to the following example, will be
generated if an optional printer is connected to the FACP.
LOOP NO.
1
1
1
Chamber Value
The Chamber value should be within the recommended range for the following smoke detectors:
The smoke detector will still function properly beyond the high limit in the above recommended
range, up to a point where the FACP issues a maintenance warning. However, it is recommended
that the smoke detectors be maintained within the recommended range to avoid maintenance warn-
ings or false alarms.
If the smoke detector's chamber reading is not within the recommended range, clean the detector
and check the chamber reading again. If the reading is still not within the recommended range, the
detector is suspect (not cleanable) and should be replaced.
Maintenance Alert
The software determines when the drift compensation for a detector reaches an unacceptable level
that can compromise detector performance. When a detector reaches an unacceptable level, the
control panel indicates a maintenance alert. Table 4.1 summarizes the three levels of maintenance
alert:
144
PRINT
1=HISTORY
2=WALKTEST LOG
3=DETECTOR DATA
Print Screen #1
DETECTOR
DETECTOR
ADDRESS
TYPE
2
SMOKE (PHOTO)
3
SMOKE (ION)
4
SMOKE (PHOTO)
SD350(T), SD355(T), D350P(R), SD300(T), AD350 and AD355 Addressable Photoelectric
Smoke Detectors: 405 - 2100 (obscuration of 1.00%/ft to 3.66%/ft.)
CP350, CP355 and CP300 Addressable Ionization Smoke Detectors: 750 - 2100 (obscuration
of 0.50%/ft. to 1.44%/ft.)
Maintenance Level
FACP Status Displays
INVREP
Low Chamber Value
DIRTY1
Maintenance Alert
Table 4.1 Maintenance Alert Levels
PRINT
1=EXIT PRINTING
Print Screen #2
CUSTOM
UPPER
CHAMBER
LABEL
LIMIT
READING
4012
1999
2844
1350
4096
1694
Indicates
A hardware problem in the detector
Dust accumulation that is near but below the allowed
limit. DIRTY 1 indicates the need for maintenance
before the performance of the detector is compromised
MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Read Status
%OBS./FT.
1.73
0.8333
1.73