GPC-3 DRH 4189340587 UK
The function of the multi-inputs can only be configured in the PC utility software.
Two alarm levels are available for each input, the menu numbers of the alarm settings for each multi-input are
controlled by the configured input type as seen in the following table.
Input type

4 to 20 mA

0 to 40 V DC

Pt100/Pt1000

RMI oil

RMI water
RMI fuel
Digital
Only one alarm level is available for the digital input type.
4.6.1 4 to 20 mA
If one of the multi-inputs has been configured as 4 to 20 mA, the unit and range of the measured value corre-
sponding to 4 to 20 mA can be changed in the PC utility software in order to get the correct reading in the
display.
4.6.2 0 to 40 V DC
The 0 to 40 V DC input has primarily been designed to handle the battery asymmetry test.

4.6.3 Pt100/1000

This input type can be used for heat sensor, for example cooling water temp. The unit of the measured value
can be changed from Celsius to Fahrenheit in the PC utility software in order to get the desired reading in the
display.

4.6.4 RMI inputs

The unit can contain up to three RMI inputs. The inputs have different functions, as the hardware design al-
lows for several RMI types.
These various types of RMI inputs are available for all multi-inputs:
RMI oil:
RMI water:
RMI fuel:
For each type of RMI input it is possible to select between different characteristics including a configurable.
4.6.5 RMI oil
This RMI input is used to measure the lubricating oil pressure.
DEIF A/S
Multi-input 102
4120/4130
4140/4150
4160/4170
4180/4190
4200/4210
4220/4230
3400
Oil pressure
Cooling water temperature
Fuel level sensor
Multi-input 105
4250/4260
4270/4280
4290/4300
4310/4320
4330/4340
4350/4360
3410
Additional functions
Multi-input 108
4380/4390
4400/4410
4420/4430
4440/4450
4460/4470
4480/4490
3420
Page 43 of 122