Group 32: Supervision

Parameters of this group are used together with relay output parameters
1401
RELAY OUTPUT
Operating Data group (Group 1) can be supervised. Relays can be
configured to be energised when the values of supervised parameters are
either too low or too high.
Code Description
3201 SUPERV 1 PARAM
First supervised parameter number of the Operating Data group (Group 01).
3202 SUPERV 1 LIM LO
First supervision limit low. Display of this parameter depends on selected super-
vised parameter (3201).
3203 SUPERV 1 LIM HI
First supervision limit high. Display of this parameter depends on selected
supervised parameter (3201).
3204 SUPERV 2 PARAM
Second supervised parameter number of the Operating Data group (Group 01).
3205 SUPERV 2 LIM LO
Second supervision limit low. Display of this parameter depends on selected
supervised parameter (3204).
3206 SUPERV 2 LIM HI
Second supervision limit high. Display of this parameter depends on selected
supervised parameter (3204).
HI (3203)
LOW (3202)
energised =1
de-energised = 0
energised =1
de-energised = 0
A = Parameter 1401
1
SUPRV
OVER
B = Parameter 1401
1
SUPRV
UNDER
Figure 14 Operating data supervision using relay outputs.
1 and 1402
RELAY OUTPUT
RELAY OUTPUT
or
2
SUPRV
OVER
RELAY OUTPUT
or
2
SUPRV
UNDER
2. Any two parameters of the
Value of supervised parameter
1 (1402
RELAY OUTPUT
1 (1402
RELAY OUTPUT
A
B
2) value is
2) value is