ABB ACS 140 Programming Manual page 42

Hide thumbs Also See for ACS 140:
Table of Contents

Advertisement

1107
EXT REF2 MIN
Sets the minimum reference in %. When analogue input signal is at minimum
value external reference 2 equals to
• If the PID Control macro is selected, this parameter sets the minimum
process reference.
• If any other macro than PID is selected, this parameter sets the minimum
frequency reference. This value is given as a percentage of the maximum
frequency.
1108
EXT REF2 MAX
Sets the maximum reference in %. When analogue input signal is at maximum,
external reference 2 equals to
• If the PID Control macro is selected, this parameter sets the maximum
process reference.
• If any other macro than PID Control is selected, this parameter sets the
maximum frequency reference. This value is given as percentage of
maximum frequency.
EXT REF
EXT REF
MAX
EXT REF
MIN
EXT REF
EXT REF
MIN
EXT REF
MAX
Figure 3
Setting
analogue input signal is set by parameters 1301 and 1302 or parameters
1304 and 1305, depending on the analogue input used.
34
EXT REF
AI min
AI min
EXT REF MINIMUM
2
. See Figure 3.
EXT REF
MIN
2
. See Figure 3.
MAX
AI max
AI max
and
EXT REF MAXIMUM
Analogue
input signal
Analogue
input signal
. The range of the