ABB ACS 140 Programming Manual page 19

Hide thumbs Also See for ACS 140:
Table of Contents

Advertisement

Code Name
Group 13
ANALOGUE INPUTS
1301
AI1
MINIMUM
Minimum value of AI1 in per cent. Defines relative analogue input
value where frequency reference reaches minimum value.
Range: 0 - 100 %
Default value: 0 %
Group 15
ANALOGUE OUTPUT
1503
AO CONTENT MAX
Defines output frequency where analogue output reaches 20 mA.
Range: 0 - 250.0 Hz.
Default value: 50.0 Hz or 60.0 Hz depending on the selected
application macro.
Note! Analogue output content is programmable. Values given here
are valid only if other analogue output configuration parameters have
not been modified. Description of all parameters is given in "ACS 140
Complete Parameter List" starting on page 23.
Group 20
LIMITS
2003
MAX CURRENT
Maximum output current.
Range: 0.5* I
Default value: 1.5 * I
2008
MAXIMUM FREQ
Maximum output frequency.
Range: 0 - 250.0 Hz
Default value: 50.0 Hz or 60.0 Hz depending on the selected
application macro.
- 1.5* I
, where I
N
N
N
N
is nominal current of the ACS 140.
The table continues on the next page.