Code Description
4013 PID SLEEP DELAY
Time delay for the sleep function, see Figure 16. If the ACS 140 output
frequency is below a set level (parameter 4014
SLEEP DELAY
4014 PID SLEEP LEVEL
Level for activation of sleep function, see Figure 16. When the ACS 140 output
frequency falls below the sleep level, the sleep delay counter is started. When
the ACS 140 output frequency rises above the sleep level, the sleep delay
counter is reset.
Note! Sleep level comparison is also inverted when error value is inverted using
parameter 4005
4015 WAKE-UP LEVEL
Level for deactivation of sleep function. This parameter sets a process actual
value limit for the sleep function (see Figure 16). When the actual value falls
below the limit, the sleep function is interrupted.
Actual Value
Frequency
SLEEP LEVEL
Parameter 4014
Figure 16
Sleep function operation.
54
, ACS 140 is stopped.
ERROR VALUE INV
-
WAKE
UP LEVEL
Parameter 4015
t
=
, Parameter 4013
SLEEP DELAY
d
t<td
SLEEP LEVEL
.
td
STOP
START
) longer than
PID
Time
Time