Group 01: Operating Data

Actual Signals monitor ACS 140 functions. They do not affect the
performance of the ACS 140. Actual Signal values are measured or
calculated by the drive and they cannot be set by the user.
Code Description
0102 SPEED
Displays the calculated speed of the motor (rpm).
0103 OUTPUT FREQ
Displays the frequency (Hz) applied to the motor. (Also shown in OUTPUT
display.)
0104 CURRENT
Displays the motor current, as measured by the ACS 140.
(The same value that is shown by the OUTPUT display mode.)
0106 POWER
Displays the measured motor power in kW.
Note! ACS100-PAN will not display the unit ("kW").
0107 DC BUS VOLTAGE
Displays the DC bus voltage, as measured by the ACS 140. The voltage is
displayed in Volts DC.
0109 OUTPUT VOLTAGE
Displays the voltage applied to the motor.
0110
ACS 140 TEMP
Displays the temperature of the ACS 140 heatsink in degrees centigrade.
0111
EXT REF 1
The value of external reference 1 in Hz.
0112
EXT REF 2
The value of external reference 2 in %.
0113
CTRL LOCATION
Displays the active control location. Alternatives are:
0 =
LOCAL
1 =
1
EXT
2 =
2
EXT
See APPENDIX for description of different control locations.
0114
RUN TIME
Shows the total running time of the ACS 140 in thousands of hours (kh).
0115
kWh COUNTER
Counts the kilowatt hours of ACS 140 in operation.
0116
APPL BLK OUTPUT
The reference value in per cent received from the application block (PID control
block). This value has significance only when the PID Control macro is used.
0117
DI1-DI4 STATUS
Status of the four digital inputs. If the input is activated, the display will indicate
1. If the input is deactivated, the display will be 0.
0118
AI1
Relative value of analogue Input 1 displayed in %.
0119
AI2
Relative value of analogue input 2 displayed in %.
28
DI 4
DI 3
DI 2
DI 1