Application Macro Alternate

This macro offers an I/O configuration that is adopted to a sequence of DI
control signals used when alternating the direction of rotation of the drive.
The value of parameter 9902 is 3.
Input signals
• Start, stop and direction (DI1,2)
• Analogue reference (AI1)
• Preset speed selection (DI3,4)
• Ramp pair 1/2 selection (DI5)
mA
*Constant speed selection: 0 = open, 1 = connected
DI3
DI4
0
0
1
0
0
1
1
1
Application macro Alternate parameter values:
9905
MOTOR NOM VOLT
9907
MOTOR NOM FREQ
9908
MOTOR NOM SPEED
1001
1
EXT
COMMANDS
1002
2
EXT
COMMANDS
1003
DIRECTION
1101
KEYPAD REF SEL
1102
1/
2
EXT
EXT
SEL
1103
1
EXT REF
SELECT
18
Output signals
Control
Terminals
1
SCR
2
AI 1
3
AGND
4
10 V
5
AI 2
6
AGND
7
AO
8
AGND
9
+12 V
10 DCOM
11 DI 1
12 DI 2
13 DI 3
14 DI 4
15 DI 5
16 DO 1A
17 DO 1B
18 DO 2A
19 DO 2B
Output
Reference through AI1
Constant speed 1 (1202)
Constant speed 2 (1203)
Constant speed 3 (1204)
230/400 V
50 Hz
1440 rpm
9 (
1
DI
0 (
NOT SEL
3 (
REQUEST
1 (
REF
6 (
EXT
1 (
1)
AI
• An. output AO: Frequency
• Relay output 1: Fault
• Relay output 2: Running
Function
External reference1; 0...10 V <=> 0...50 Hz
Reference voltage 10 VDC
Not used
Output frequency 0...20 mA <=> 0...50 Hz
+12 VDC
Start fwd; If DI1 state is the same as DI2, drive stops
Start reverse
Constant speed select*
Constant speed select*
Ramp pair selection. Activate to select ramp
pair 2. Defaults: 5 s / 60 s (ramp pair 1/2)
1105
EXT REF
1106
EXT REF
1201
CONST SPEED SEL
,2
)
1503
F
R
AO CONTENT MAX
)
1601
RUN ENABLE
)
2008
MAXIMUM FREQ
1)
2105
PREMAGN SEL
1)
2201
ACC
U/I jumper S1
S1:1:U
Relay output 1
Relay output 2
Running: closed
1
MAX
2
SELECT
/
1/2
DEC
SEL
Fault: open
50 Hz
0 (
)
KEYPAD
7 (
3,4)
DI
50 Hz
0 (
)
NOT SEL
50 Hz
0 (
)
NOT SEL
5 (
5)
DI