Group 14: Relay Outputs

Code Description
1401 RELAY OUTPUT 1
Relay output 1 content.
Selects which information is indicated with relay output 1.
0 =
NOT SEL
Relay is not used and is de-energised.
1 =
READY
The ACS 140 is ready to function. The relay is energised unless no run enable
signal is present or a fault exists and supply voltage is within range.
2 =
RUN
Relay energised when the ACS 140 is running.
3 =
(-1)
FAULT
Relay energised when power is applied, and de-energised upon a fault trip.
4 =
FAULT
Relay energised when a fault is active.
5 =
ALARM
Relay energised when an alarm (AL10-22) is active.
6 =
REVERSED
Relay energised when motor rotates in reverse direction.
7 =
1
SUPRV
Relay energised when first supervised parameter (3201) exceeds the limit
(3203). See "Group 32: Supervision", starting page 49.
8 =
1
SUPRV
Relay energised when first supervised parameter (3201) drops below the limit
(3202). See "Group 32: Supervision", starting page 49.
9 =
2
SUPRV
Relay energised when second supervised parameter (3204) exceeds the limit
(3206). See "Group 32: Supervision", starting page 49.
10 =
2
SUPRV
Relay energised when second supervised parameter (3204) drops below the
limit (3205). See "Group 32: Supervision", starting page 49.
11 =
AT SET POINT
Relay energised when output frequency is equal to reference frequency.
1402 RELAY OUTPUT 2
Relay output 2 content. Refer to parameter 1401
OVER
UNDER
OVER
UNDER
1.