Basic Programming; Commissioning With Smartstart; Commissioning Via [Main Menu] - Danfoss VLT AQUA FC 202 Operating Instructions Manual

0.25-90 kw
Hide thumbs Also See for VLT AQUA FC 202:
Table of Contents

Advertisement

Commissioning
Recommended initialisation procedure, via
14-22 Operation Mode
1.
Press [Main Menu] twice to access parameters.
2.
Scroll to 14-22 Operation Mode and press [OK].
3.
Scroll to Initialisation and press [OK].
4.
Remove power to the unit and wait for the
display to turn off.
5.
Apply power to the unit.
Default parameter settings are restored during start-up.
This may take slightly longer than normal.
5
5
6.
Alarm 80 is displayed.
7.
Press [Reset] to return to operation mode.
Manual initialisation procedure
1.
Remove power to the unit and wait for the
display to turn off.
2.
Press and hold [Status], [Main Menu], and [OK] at
the same time while applying power to the unit
(approximately 5 s or until audible click and fan
starts).
Factory default parameter settings are restored during
start-up. This may take slightly longer than normal.
Manual initialisation does not reset the following frequency
converter information:
Parameter 15-00 Operating hours
Parameter 15-03 Power Up's
Parameter 15-04 Over Temp's
Parameter 15-05 Over Volt's

5.4 Basic Programming

5.4.1 Commissioning with SmartStart

The SmartStart wizard enables fast configuration of basic
motor and application parameters.
SmartStart starts automatically, at first power up
or after initialisation of the frequency converter.
Follow the on-screen instructions to complete the
commissioning of the frequency converter.
Always reactivate SmartStart by selecting Quick
Menu Q4 - SmartStart.
For commissioning without use of the SmartStart
wizard, refer to chapter 5.4.2 Commissioning via
[Main Menu] or the Programming Guide.
NOTICE
Motor data is required for the SmartStart set-up. The
required data is normally available on the motor
nameplate.
24
Operating Instructions
The SmartStart configures the frequency converter in 3
phases, each consisting of several steps, see Table 5.6.
Table 5.6 SmartStart, Setup in 3 Phases

5.4.2 Commissioning via [Main Menu]

Recommended parameter settings are intended for start-
up and checkout purposes. Application settings may vary.
Enter data with power ON, but before operating the
frequency converter.
Illustration 5.2 Main Menu
Illustration 5.3 Operation/Display
Danfoss A/S © Rev. 05/2014 All rights reserved.
Phase
1
Basic Programming
2
Application Section
3
Water and Pump Features
1.
Press [Main Menu] on the LCP.
2.
Press the navigation keys to scroll to parameter
group 0-** Operation/Display and press [OK].
1107 RPM
Main menu
0 - ** Operation/Display
1 - ** Load/Motor
2 - ** Brakes
3 - ** Reference / Ramps
3.
Press the navigation keys to scroll to parameter
group 0-0* Basic Settings and press [OK].
0.0%
Operation / Display
0-0
Basic Settings
*
0-1
*
Set-up Operations
0-2
*
LCP Display
0-3
*
LCP Custom Readout
4.
Press the navigation keys to scroll to
0-03 Regional Settings and press [OK].
Comment
Programme e.g. motor data
Select and programme
appropriate application:
Single pump/motor
Motor alternation
Basic cascade control
Master/follower
Go to water and pump
dedicated parameters.
3.84 A
1 (1)
0.00A
1(1)
0-
**
MG20MB02