Application Set-up Examples

6 Application Set-up Examples
The examples in this section are intended as a quick
reference for common applications.
Parameter settings are the regional default values
unless otherwise indicated (selected in parameter
0-03 Regional Settings).
Parameters associated with the terminals and
their settings are shown next to the drawings.
Where switch settings for analog terminals A53 or
A54 are required, these are also shown.
6
6
NOTICE
When the optional Safe Torque Off feature is used, a
jumper wire may be required between terminal 12 (or
13) and terminal 37 for the frequency converter to
operate when using factory default programming values.
6.1 Application Examples
6.1.1 Feedback
FC
12
+24 V
13
+24 V
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
33
D IN
37
D IN
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
U - I
A 54
Table 6.1 Analog Current Feedback Transducer
28
Operating Instructions
Parameters
Function
6-22 Terminal 54
Low Current
6-23 Terminal 54
High Current
6-24 Terminal 54
Low Ref./Feedb.
Value
6-25 Terminal 54
High Ref./Feedb.
Value
* = Default Value
Notes/comments:
+
D IN 37 is an option.
-
4-20 mA
Danfoss A/S © Rev. 05/2014 All rights reserved.
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
U - I
A54
Setting
4 mA*
Table 6.2 Analog Voltage Feedback Transducer (3-wire)
20 mA*
FC
0*
+24 V
12
+24 V
13
D IN
18
50*
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
U - I
A54
Table 6.3 Analog Voltage Feedback Transducer (4-wire)
Parameters
Function
Setting
6-20 Terminal 54
0.07 V*
Low Voltage
6-21 Terminal 54
10 V*
High Voltage
6-24 Terminal 54
0*
Low Ref./Feedb.
Value
6-25 Terminal 54
50*
High Ref./Feedb.
Value
* = Default Value
+
Notes/comments:
D IN 37 is an option.
-
0 - 10V
Parameters
Function
Setting
6-20 Terminal 54
0.07 V*
Low Voltage
6-21 Terminal 54
10 V*
High Voltage
6-24 Terminal 54
0*
Low Ref./Feedb.
Value
6-25 Terminal 54
50*
High Ref./Feedb.
Value
* = Default Value
+