Danfoss VLT AQUA FC 202 Operating Instructions Manual page 68

0.25-90 kw
Hide thumbs Also See for VLT AQUA FC 202:
Table of Contents

Advertisement

Specifications
380-480 V, Enclosure Types A, B, and C
Enclosure
A2
A3
A4
A5
B1
B2
B3
B4
C1
8
8
C2
C3
C4
Table 8.20 380-480 V, Enclosure Types A, B, and C
66
Power [kW]
Recommended
fuse size
1.1-4.0
gG-10 (0.37-3)
gG-16 (4)
5.5-7.5
gG-16
1.1-4.0
gG-10 (0.37-3)
gG-16 (4)
1.1-7.5
gG-10 (0.37-3)
gG-16 (4-7.5)
11-18.5
gG-40
22-30
gG-50 (18.5)
gG-63 (22)
11-18
gG-40
22-37
gG-50 (18.5)
gG-63 (22)
gG-80 (30)
37-55
gG-80 (30)
gG-100 (37)
gG-160 (45)
75-90
aR-200 (55)
aR-250 (75)
45-55
gG-100 (37)
gG-160 (45)
75-90
aR-200 (55)
aR-250 (75)
Danfoss A/S © Rev. 05/2014 All rights reserved.
Operating Instructions
Recommended
maximum fuse
gG-25
gG-32
gG-32
gG-32
gG-80
gG-100
gG-63
gG-125
gG-160
aR-250
gG-150 (37)
gG-160 (45)
aR-250
Recommended circuit
Maximum trip level
breaker
Moeller
PKZM0-25
PKZM0-25
PKZM0-25
PKZM0-25
PKZM4-63
NZMB1-A100
PKZM4-50
NZMB1-A100
NZMB2-A200
NZMB2-A250
NZMB2-A200
NZMB2-A250
[A]
25
25
25
25
63
100
50
100
160
250
150
250
MG20MB02