Electrical Installation
1
12 13 18 19 27 29 32 33 20 37
2
3
39 42 50 53 54 55
61 68 69
Illustration 4.8 Terminal Numbers
Connector 1 provides:
-
4 programmable digital inputs terminals.
-
2 additional digital terminals
programmable as either input or output.
-
24 V DC terminal supply voltage.
-
Optional customer supplied 24 V DC
voltage.
Connector 2 terminals (+)68 and (-)69 are for an
RS-485 serial communication connection.
Connector 3 provides:
-
2 analog inputs.
-
1 analog output.
-
10 V DC supply voltage.
-
Commons for the inputs and output.
Connector 4 is a USB port available for use with
the MCT 10 Set-up Software.
Terminal description
Default
Terminal
Parameter
setting
Digital Inputs/Outputs
12, 13
-
+24 V DC
18
5-10
[8] Start
19
5-11
[0] No
operation
32
5-14
[0] No
operation
33
5-15
[0] No
operation
27
5-12
[2] Coast
inverse
29
5-13
[14] JOG
MG20MB02
Operating Instructions
Description
24 V DC supply voltage
for digital inputs and
external transducers.
Maximum output
current 200 mA for all
24 V loads.
Additional terminals:
Digital inputs.
For digital input or
output. Default setting
is input.
Danfoss A/S © Rev. 05/2014 All rights reserved.
Terminal description
Default
Terminal
Parameter
setting
20
-
37
-
Safe Torque
Off (STO)
Analog Inputs/Outputs
39
-
42
6-50
Speed 0 -
High Limit
50
-
+10 V DC
53
6-1
Reference
54
6-2
Feedback
55
-
Serial Communication
61
-
68 (+)
8-3
69 (-)
8-3
Relays
01, 02, 03
5-40 [0]
[9] Alarm
04, 05, 06
5-40 [1]
[5] Running
Table 4.2 Terminal Description
2 form C relay outputs. Location of the outputs
depends on frequency converter configuration.
Terminals located on built-in optional equipment.
See the manual provided with the equipment
option.
Description
Common for digital
inputs and 0 V
potential for 24 V
supply.
4
Safe input (optional).
Used for STO.
Common for analog
output
Programmable analog
output. 0-20 mA or
4-20 mA at a maximum
of 500 Ω
10 V DC analog supply
voltage for potenti-
ometer or thermistor.
15 mA maximum
Analog input. For
voltage or current.
Switches A53 and A54
select mA or V.
Common for analog
input
Integrated RC-Filter for
cable screen. ONLY for
connecting the screen
in the event of EMC
problems.
RS-485 Interface. A
control card switch is
provided for
termination resistance.
Form C relay output.
For AC or DC voltage
and resistive or
inductive loads.
17
4

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents