Danfoss VLT AQUA FC 202 Operating Instructions Manual page 40

0.25-90 kw
Hide thumbs Also See for VLT AQUA FC 202:
Table of Contents

Advertisement

Maintenance, Diagnostics an...
Troubleshooting
Check the fan resistance.
Check the soft charge fuses.
Check the IGBT thermal sensor.
ALARM 30, Motor phase U missing
Motor phase U between the frequency converter and the
motor is missing.
Troubleshooting
Remove power from the frequency converter and
check motor phase U.
ALARM 31, Motor phase V missing
Motor phase V between the frequency converter and the
motor is missing.
Remove power from the frequency converter and check
motor phase V.
7
7
ALARM 32, Motor phase W missing
Motor phase W between the frequency converter and the
motor is missing.
Remove power from the frequency converter and check
motor phase W.
ALARM 33, Inrush fault
Too many power-ups have occurred within a short time
period. Let the unit cool to operating temperature.
WARNING/ALARM 34, Fieldbus communication fault
The fieldbus on the communication option card is not
working.
WARNING/ALARM 36, Mains failure
This warning/alarm is only active if the supply voltage to
the frequency converter is lost and 14-10 Mains Failure is
NOT set to [0] No Function.
Troubleshooting
Check the fuses to the frequency converter and
mains power supply to the unit.
ALARM 38, Internal fault
When an internal fault occurs, a code number defined in
the Table 7.4 is displayed.
Troubleshooting
Cycle power.
Check that the option is properly installed.
Check for loose or missing wiring.
Contact the Danfoss supplier or Danfoss service if required.
Note the code number for further troubleshooting
directions.
No.
Text
0
Serial port cannot be initialised. Contact the
Danfoss supplier or Danfoss Service.
256-258
Power EEPROM data is defective or too old.
512
Control board EEPROM data is defective or too
old.
38
Operating Instructions
1024-1279
2064-2072
2080-2088
2096-2104
Danfoss A/S © Rev. 05/2014 All rights reserved.
No.
Text
513
Communication time out reading EEPROM data.
514
Communication time out reading EEPROM data.
515
Application oriented control cannot recognize the
EEPROM data.
516
Cannot write to the EEPROM because a write
command is on progress.
517
Write command is under time out.
518
Failure in the EEPROM.
519
Missing or invalid barcode data in EEPROM.
783
Parameter value outside of min/max limits.
A centelegram that has to be sent couldn't be
sent.
1281
Digital signal processor flash timeout.
1282
Power micro software version mismatch.
1283
Power EEPROM data version mismatch.
1284
Cannot read digital signal processor software
version.
1299
Option SW in slot A is too old.
1300
Option SW in slot B is too old.
1301
Option SW in slot C0 is too old.
1302
Option SW in slot C1 is too old.
1315
Option SW in slot A is not supported (not
allowed).
1316
Option SW in slot B is not supported (not
allowed).
1317
Option SW in slot C0 is not supported (not
allowed).
1318
Option SW in slot C1 is not supported (not
allowed).
1379
Option A did not respond when calculating
platform version.
1380
Option B did not respond when calculating
platform version.
1381
Option C0 did not respond when calculating
platform version.
1382
Option C1 did not respond when calculating
platform version.
1536
An exception in the application oriented control is
registered. Debug information written in LCP.
1792
DSP watchdog is active. Debugging of power part
data, motor oriented control data not transferred
correctly.
2049
Power data restarted.
H081x: option in slot x has restarted.
H082x: option in slot x has issued a power-up
wait.
H983x: option in slot x has issued a legal power-
up wait.
2304
Could not read any data from power EEPROM.
2305
Missing SW version from power unit.
2314
Missing power unit data from power unit.
2315
Missing SW version from power unit.
2316
Missing lo_statepage from power unit.
MG20MB02