Danfoss VLT AQUA FC 202 Operating Instructions Manual page 54

0.25-90 kw
Hide thumbs Also See for VLT AQUA FC 202:
Table of Contents

Advertisement

Specifications
Type designation
High/normal overload
Typical shaft output [kW]
Typical shaft output at 460 V [hp]
6)
IP20/Chassis
IP21/Type 1
IP55/Type 12
IP66/NEMA 4X
Output current
Continuous (3x380-440 V) [A]
Intermittent (60 s overload)
(3x380-440 V) [A]
Continuous (3x441-480 V) [A]
Intermittent (60 s overload)
(3x441-480 V) [A]
Continuous kVA at 400 V [kVA]
Continuous kVA at 460 V [kVA]
Maximum input current
Continuous (3x380-440 V) [A]
Intermittent (60 s overload)
8
8
(3x380-440 V) [A]
Continuous (3x441-480 V) [A]
Intermittent (60 s overload)
(3x441-480 V) [A]
Maximum pre-fuses [A]
Additional specifications
IP20 maximum cable cross-section
for mains and motor [mm
IP20 maximum cable cross-section
for brake and load sharing
2
[mm
] ([AWG])
IP21, IP55, IP66 maximum cable
cross-section for mains and motor
[mm
2
] ([AWG])
IP21, IP55, IP66 maximum cable
cross-section for brake and load
2
sharing [mm
] ([AWG])
Maximum cable cross-section
mains disconnect
2
[mm
] ([AWG])
Estimated power loss
at rated maximum load [W]
Efficiency
4)
Table 8.10 Mains Supply 3x380-480 V AC, P37K-P90K
For fuse ratings see chapter 8.8 Fuses and Circuit Breakers.
1) High overload=150% or 160% torque for a duration of 60 s. Normal overload=110% torque for a duration of 60 s.
2) The 3 values for the maximum cable cross-section indicate single core, flexible wire, and flexible wire with sleeve, respectively.
3) The typical power loss is at normal load conditions and expected to be within
conditions).
Values are based on typical motor efficiency. Lower efficiency motors will also add to the power loss in the frequency converter and vice versa.
If the switching frequency is raised from nominal, power losses may rise significantly.
LCP and typical control card power consumption is included. Further options and customer load may add up to 30 W to the losses. (Though
typically only 4 W extra each for options for slot A or B, or for a fully loaded control card).
Although measurements are made with state-of-the-art equipment, some measurement inaccuracy must be allowed for (
52
Operating Instructions
P37K
1)
HO
NO
30
37
40
50
B4
C1
C1
61
73
91.5
80.3
52
65
78
71.5
42.3
50.6
41.4
51.8
55
66
82.5
72.6
47
59
70.5
64.9
100
35 (2)
2
] ([AWG])
35 (2)
50 (1)
50 (1)
2)
for
3)
570
698
0.98
Danfoss A/S © Rev. 05/2014 All rights reserved.
P45K
P55K
HO
NO
HO
NO
37
45
45
55
50
60
60
75
C3
C3
C1
C1
C1
C1
73
90
90
106
110
99
135
117
65
80
80
105
97.5
88
120
116
50.6
62.4
62.4
73.4
51.8
63.7
63.7
83.7
66
82
82
96
99
90.2
123
106
59
73
73
95
88.5
80.3
110
105
125
160
50 (1)
50 (1)
50 (1)
50 (1)
50 (1)
50 (1)
50 (1)
50 (1)
50, 35, 35
(1, 2, 2)
697
843
891
1083
0.98
0.98
± 15% (tolerance relates to variations in voltage and cable
P75K
P90K
HO
NO
HO
NO
55
75
75
90
75
100
100
125
C4
C4
C2
C2
C2
C2
106
147
147
177
159
162
221
195
105
130
130
160
158
143
195
176
73.4
102
102
123
83.7
104
103.6
128
96
133
133
161
144
146
200
177
95
118
118
145
143
130
177
160
250
250
150 (300 MCM)
150 (300 MCM)
95 (4/0)
95 (4/0)
150 (300 MCM)
150 (300 MCM)
95 (3/0)
95 (3/0)
185, 150, 120
95, 70, 70
(350 MCM, 300
(3/0, 2/0, 2/0)
MCM, 4/0)
1022
1384
1232
1474
0.98
0.99
± 5%).
MG20MB02