11.5 Depth dimensions for the GOT with several extension units mounted in
multiple stages (GT27, GT25)
The following shows how to calculate the depth dimensions for the GOT with several extension units mounted in multiple
stages.
For the dimensions for the GOT with one extension unit, refer to the dimension D in
Radius for GT27 with an Extension Unit.
Step 1.
Select the GOT main unit coefficient from the following table.
GT27, GT25
Step 2.
Select the option coefficient of the extension unit from the following table.
GT25-J71E71-100
*1*2
GT27-V4-Z
, GT27-R2-Z
GT15-QBUS, GT15-QBUS2, GT15-RS2-9P, GT15-RS4-9S, GT15-RS4-TE,
GT15-J71LP23-25, GT15-J71BR13, GT15-J61BT13, GT15-PRN, GT15-DIO,
GT15-DIOR, GT15-SOUT
*1*2
GT27-MMR-Z
GT15-J71GP23-SX *1, GT15-J71GF13-T2
*1
Mounting GT27-V4-Z, GT27-R2-Z, GT27-V4R1-Z, GT27-ROUT-Z, or GT27-MMR-Z requires two stages. When mounting GT15-
J71GP23-SX or GT15-J71GF13-T2 on any of the above units, mount it in the third stage.
*2
The extension unit cannot be used on GT2705, GT2512, GT2510, or GT2508.
Step 3.
Substitute the coefficients selected in step 1 and step 2 to the following formula.
E (for two extension units) = G (GOT main unit coefficient) + H (option coefficient) + H (option coefficient)
F (for three extension units) = G (GOT main unit coefficient) + H (option coefficient) + H (option coefficient)
+ H (option coefficient)
Calculation example:
Dimension F (for three extension units) for installing the multimedia unit (GT27-MMR-Z) in the first stage
and the second stage, and the CC-Link IE Controller Network communication unit (GT15-J71GP23-SX) in
the third stage on the GT2712
F (for three extension units) = -3.5 (main unit coefficient of GT2712) + 57.0(option coefficient of GT27-MMR-
Z) + 35.5 (option coefficient of GT15-J71GP23-SX) = 89.0
When the above two extension units are installed, the dimension F is 89.0 mm.

11.5 Depth dimensions for the GOT with several extension units mounted in multiple stages (GT27, GT25)

100 (3.94)or more
E
F
GOT type
Model
*1*2
*1*2
, GT27-V4R1-Z
, GT27-ROUT-Z
*1
11.2
Other device
Unit: mm (inch)
G (main unit coefficient)
1.5(0.06)
*1*2
Depth Dimensions and Cable Bend
H (option coefficient)
18.5(0.73)
43.0(1.69)
21.5(0.85)
57.0(2.24)
35.5(1.40)