Gt21 - Mitsubishi Electric GOT2000 Series User Manual

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

3.1.3

GT21

Item
Operating ambient temperature
Storage ambient temperature
Operating ambient humidity
Storage ambient humidity
Vibration resistance
Shock resistant
Operating atmosphere
*3
Operating altitude
Installation location
*4
Overvoltage category
*5
Pollution degree
Cooling method
Grounding
*1
*2
*3
*4
*5
*6
The 5V DC type does not require to be grounded.
3 - 4
3.1 General Specifications
*1
Compliant with
JIS B 3502 and
IEC 61131-2
Compliant with JIS B 3502 and IEC 61131-2 (147 m/s
No greasy fumes, corrosive gas, flammable gas, excessive conductive dust,
For GT2107 and GT2105: Grounding with a ground resistance of 100 Ω or less by using a ground cable that has a
diameter of 1.6 mm or more. If impossible, connect the ground cable to the control panel.
For GT2104 and GT2103: Grounding with a ground resistance of 100 Ω or less by using a ground cable that has a
cross-sectional area of 0.14 to 1.5 mm
with an insulation sleeve). If impossible, connect the ground cable to the control panel.
Includes the temperature inside the enclosure of the control panel on which the GOT is installed.
If the ambient temperature exceeds 40 °C, the absolute humidity must not exceed 90% at 40 °C.
Do not use or store the GOT under a pressure higher than the atmospheric pressure at altitude 0 m.
Doing so may cause a malfunction.
Air purging by applying pressure to the control panel may create clearance between the surface sheet and the touch panel. This
may cause the touch panel to be not sensitive enough or the sheet to come off.
This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical
power distribution network and the machinery within the premises.
Category II applies to equipment for which electrical power is supplied from fixed facilities.
The withstand surge voltage for the equipment with the rated voltage up to 300 V is 2500 V.
This indicates the occurrence rate of conductive material in an environment where a device is used. Pollution degree 2 indicates
an environment where only non-conductive pollution occurs normally and a temporary conductivity caused by condensation shall
be expected depending on the conditions.
Specifications
0°C to 55°C (Horizontal installation), 0°C to 50°C (Vertical installation)
-20°C to 60°C
10% RH to 90% RH, non-condensing
10% RH to 90% RH, non-condensing
Frequency
Under
5 to 8.4 Hz
intermittent
8.4 to 150 Hz
vibration
Under
5 to 8.4 Hz
continuous
8.4 to 150 Hz
vibration
and direct sunlight (as well as at storage)
2000 m or less
Inside control panel
II or less
2 or less
Self-cooling
2
(solid wire), 0.14 to 1.0 mm
*2
*2
Acceleration
Half amplitude
-
3.5 mm
9.8 m/s2
-
-
1.75 mm
4.9 m/s2
-
2
(15G), 3 times in each X, Y, or Z direction)
2
(stranded wire), or 0.25 to 0.5 mm
Sweep count
10 times in each
X, Y, or Z
direction
-
2
(rod terminal
*6