6.5.3

GT23

■1. GT23
Regardless of the installation orientation, install the GT23 so that the following conditions are satisfied.
When the GOT is installed at any angle from 60 ° to 105 °, the control panel inside temperature must be within 55 °C.
When the GOT is installed at any angle outside the range from 60 ° to 105 °, the control panel inside temperature must
be within 40 °C.
6.5.4

GT21

Install the GOT with its display section positioned as shown below.
Using the GOT with the installation angle other than the following accelerates the deterioration of the GOT.
■1. GT21
(1) Installing the GOT horizontally
When the GOT is installed at any angle from 60 ° to 105 °, the control panel inside temperature must be within 55 °C.
When the GOT is installed at any angle outside the range from 60 ° to 105 °, the control panel inside temperature
must be within 40 °C.
(2) Installing the GOT vertically
When the GOT is installed at any angle from 60 ° to 105 °, the control panel inside temperature must be within 50 °C.
When the GOT is installed at any angle outside the range from 60 ° to 105 °, the control panel inside temperature
must be within 40 °C.
6 - 22
6.5 Control Panel Inside Temperature and GOT Installation Angle
GOT
Display
section
Control panel
or others
GOT
Display
section
Control panel
or others
GOT
Display
section
Control panel
or others
105°
60°
105°
60°
105°
60°