2.6.1 Connecting a Chassis Ground Cable

Take the following steps to connect a ground cable from the HN4000 chassis to an earth 
ground.
The HN4000 must be permanently grounded to a Common Bonding Network (CBN).
Grounding of the HN4000 should be in compliance with local practices and must be to a protective
earth ground (clean, bare-metal).
Caution
The grounding connection must be made before copper-pair connections are made to the
device's 2BASE-TL connectors.
Step 1. Measure to determine the length of grounding cable required to run from the chassis' 
ground lug (Figure
Figure 2-7
HN4000
Step  2. Cut a length of 10 ‐ 14 AWG (2.6 ‐ 1.6 mm) stranded/insulated wire to that length.
Your local electrical code may require that a specific color (or colors) be used for the
Note
protective-earth ground wire.
Step  3. Remove the two 3/8 inch hex nuts from the ground lug's grounding studs and remove 
the ground lug.
Step  4. Strip one end of the cable (approximately 3/8" (1.0 cm)) to fit into the ground lug.
Step  5. Using a crimping tool, crimp the HN4000 ground lug to the cable.
Step  6. Replace the ground lug onto the grounding studs and fasten with the two 3/8 inch 
hex nuts. Tighten the hex nuts to 20 ‐ 27 in‐lbs (2.3 ‐ 3.0 Nm).
Step  7. Dress the cable through a cable‐guide slot in the chassis' right‐hand bracket.
Step  8. Terminate the unterminated end of the grounding cable in compliance with local 
practices and fasten it to the grounding point on the fuse/breaker panel.
End of Procedure
920550-5020 Rev 14
2‐7) and a grounding point on the rack's fuse/breaker panel.
 
Ground Lug
Installing the Ground and Power Cables
Ground Lug
HN4000 Hardware Installation Guide