Ring - Siemens SCALANCE X-200 Configuration Manual

Industrial ethernet switches
Hide thumbs Also See for SCALANCE X-200:
Table of Contents

Advertisement

Syntax of the Command Line Interface
Table 5- 11
Command
info
fault
power [<E|D> [lines]]
others <R|S|F> <E|D>
downmask <1-n> <E|D>
upmask <1-n> <E|D>
5.2.3

Ring

Ring redundancy
On this page, you can set the ports for media redundancy and the required redundancy
mode.
Note
X-200 IE switches as of firmware V4.0 support the media redundancy methods MRP and
HRP.
X-200 IE switches with firmware V3.1 and older, X-300 and X-400 IE switches with firmware
V2.3 and older and OSMs/ESMs support only the HRP method.
Note
If you want to configure an MRP ring, the devices can be interconnected to form a ring
without any extra configuration. In this case, the default ring ports must be used, see
Appendix Default ring ports (Page 177). The default role "Automatic Redundancy Detection"
automatically configures the ring.
If an HRP ring is configured, exactly one device in the ring must be set to the HRP Manager
role. All other devices in the ring must be set to either "Automatic Redundancy Detection" or
"HRP Client".
If an HRP ring is configured in which a linear bus is set up in which a device is set to HRP
manager and the other devices have the setting "Automatic Redundancy Detection", the
error message "other RM in ring" is output. This disappears after connecting the linear bus to
form a ring.
SCALANCE X-200
Configuration Manual, 03/2015, C79000-G8976-C285-06
Fault Mask - CLI\X200>
Description
Displays information on the "X-200" menu item.
Displays the fault status.
Specifies a fault mask for the power supplies Power
Line 1 and Power Line 2.
Specifies the fault mask for:
R - Ring Redundancy Manager
S - Standby Manager (only relevant for IRT devices)
F - FMP Event (only relevant for FM devices)
Specifies a port mask for the ports for which the
monitoring of a link down event is enabled.
Specifies a port mask for the ports for which the
monitoring of a link up event is enabled.
Menus in the WBM
5.2 The X-200 menu
Comment
Administrator only
Administrator only
Administrator only
Administrator only
71

Hide quick links:

Advertisement

Table of Contents
loading