Menus in the WBM
5.3 The Agent menu
Redundancy Event
A redundancy event is triggered:
● When the redundant connection is opened or closed
● When a second ring manager is identified.
Standby Event (relevant for IRT devices only)
A standby event is triggered
● When the standby connection is opened or closed
● When the standby partner is lost or returns.
Loop detection
A loop was detected in the network.
FMP Event (only relevant for FM devices, refer to the section "FMP (Page 119)")
The value of the received power or the power loss has exceeded a certain limit.
POF Event (only relevant for devices with POF functionality, refer to the section "POF
(Page 129)")
The value of the received power or the power loss has fallen below a certain limit.
Signaling Contact Control
With this drop-down list, you can specify how the signaling contact works:
● conventional
Default setting for the signaling contact. An error/fault is displayed by the fault LED and
the signaling contact opens. When the error/fault state no longer exists, the fault LED
goes off and the signaling contact closes.
● aligned
The way the signaling contact works depends on the error/fault that has occurred. The
signaling contact can be opened or closed as required by user actions.
Close Signaling Contact
Select this check box if you want to close the signaling contact.
Note
The setting of the "Close Signaling Contact" check box is only effective if the "aligned"
setting was selected in the "Signaling Contact Control" drop-down list.