806f0a0c-2027ffff • 806f0a0c-2028ffff
SNMP Trap ID: 0
Automatically notify Support: No
User response: Complete the following steps:
1. Check the CMM or FSM event log for any fan or cooling related issues.
2. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are in place and
correctly installed.
3. Make sure that the room temperature is within operating specifications.
4. Make sure that the DIMM baffles are in place.
5. If the problem persists and there are no other DIMMs with the same indication, replace the DIMM.
806f0a0c-2027ffff
An Over-Temperature Condition has been detected on the [PhysicalMemoryElementName] on
Subsystem [MemoryElementName].
Explanation: An over temperature condition for memory has been detected.
May also be shown as 806f0a0c2027ffff or 0x806f0a0c2027ffff
Severity: Error
Alert Category: Critical - Temperature
Serviceable: Yes
CIM Information: Prefix: PLAT and ID: 0146
SNMP Trap ID: 0
Automatically notify Support: No
User response: Complete the following steps:
1. Check the CMM or FSM event log for any fan or cooling related issues.
2. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are in place and
correctly installed.
3. Make sure that the room temperature is within operating specifications.
4. Make sure that the DIMM baffles are in place.
5. If the problem persists and there are no other DIMMs with the same indication, replace the DIMM.
806f0a0c-2028ffff
An Over-Temperature Condition has been detected on the [PhysicalMemoryElementName] on
Subsystem [MemoryElementName].
Explanation: An over temperature condition for memory has been detected.
May also be shown as 806f0a0c2028ffff or 0x806f0a0c2028ffff
Severity: Error
Alert Category: Critical - Temperature
Serviceable: Yes
CIM Information: Prefix: PLAT and ID: 0146
SNMP Trap ID: 0
Automatically notify Support: No
User response: Complete the following steps:
1. Check the CMM or FSM event log for any fan or cooling related issues.
2. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are in place and
correctly installed.
3. Make sure that the room temperature is within operating specifications.
4. Make sure that the DIMM baffles are in place.
5. If the problem persists and there are no other DIMMs with the same indication, replace the DIMM.
498