Lenovo Flex System x280 X6 Compute Node Installation And Service Manual page 498

Types 7903 and 4259
Hide thumbs Also See for Flex System x280 X6 Compute Node:
Table of Contents

Advertisement

806f0a0c-200affff • 806f0a0c-200bffff
SNMP Trap ID: 0
Automatically notify Support: No
User response: Complete the following steps:
1. Check the CMM or FSM event log for any fan or cooling related issues.
2. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are in place and
correctly installed.
3. Make sure that the room temperature is within operating specifications.
4. Make sure that the DIMM baffles are in place.
5. If the problem persists and there are no other DIMMs with the same indication, replace the DIMM.
806f0a0c-200affff
An Over-Temperature Condition has been detected on the [PhysicalMemoryElementName] on
Subsystem [MemoryElementName].
Explanation: An over temperature condition for memory has been detected.
May also be shown as 806f0a0c200affff or 0x806f0a0c200affff
Severity: Error
Alert Category: Critical - Temperature
Serviceable: Yes
CIM Information: Prefix: PLAT and ID: 0146
SNMP Trap ID: 0
Automatically notify Support: No
User response: Complete the following steps:
1. Check the CMM or FSM event log for any fan or cooling related issues.
2. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are in place and
correctly installed.
3. Make sure that the room temperature is within operating specifications.
4. Make sure that the DIMM baffles are in place.
5. If the problem persists and there are no other DIMMs with the same indication, replace the DIMM.
806f0a0c-200bffff
An Over-Temperature Condition has been detected on the [PhysicalMemoryElementName] on
Subsystem [MemoryElementName].
Explanation: An over temperature condition for memory has been detected.
May also be shown as 806f0a0c200bffff or 0x806f0a0c200bffff
Severity: Error
Alert Category: Critical - Temperature
Serviceable: Yes
CIM Information: Prefix: PLAT and ID: 0146
SNMP Trap ID: 0
Automatically notify Support: No
User response: Complete the following steps:
1. Check the CMM or FSM event log for any fan or cooling related issues.
2. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are in place and
correctly installed.
3. Make sure that the room temperature is within operating specifications.
4. Make sure that the DIMM baffles are in place.
5. If the problem persists and there are no other DIMMs with the same indication, replace the DIMM.
486
Flex System x280 X6, x480 X6, and x880 X6 Compute Node Types 7903 and 4259: Installation and Service Guide

Advertisement

Table of Contents
loading

Table of Contents