Other Points To Note - Mitsubishi Electric AE-200A Service Handbook

Hide thumbs Also See for AE-200A:
Table of Contents

Advertisement

[III System restrictions and notes]

[9] Other points to note

(1) About using General equipment
・ There may be cases when the general equipment cannot be monitored or operated due to, for example, a disconnection of the
wiring between the general equipment or a failure of the DIDO controller or PLC. In such a case, Mitsubishi Electric will not be held
liable in the event of any damages. We recommend providing a circuit that enables emergency remedial operation, etc. to be
performed when a failure occurs.
・ With the Ver.1 series of General Control PLC Software, the license number does not need to be registered to the
AE-200/AE-50/EW-50.
・ With the Ver.2 series of General Control PLC Software, General Control PLC Software License is not required to operate and
monitor general equipment and use the schedule functions, but TG-2000A is required.
To use interlock control, General Control PLC Software License is required for each AE-200/AE-50/EW-50.
General Control PLC Software License is required even for interlock control within the PLC.
・ A license number does not need to be registered to, for example, operate general equipment with a DIDO controller.
(2) About USB memory devices
● Select a USB memory device that meets the following conditions and verify operation several times before use.
* Reading and writing with a memory device for which operation has not been verified may cause an unexpected operation.
Therefore, verify operation of the memory device (during trial operation) before use.
Do not use a USB memory device for which a data writing error has occurred.
1.
USB standard: Supports USB 2.0.
2.
Formatted with FAT32 or FAT (FAT16)
3.
Security function is not provided or not required to be set.
(Depending on the security function, there may also be some USB devices for which use is possible.)
In cases such as when data writing can still not be performed normally when a USB memory device has been replaced with
another one after a data error occurs, restart the AE-200/AE-50/EW-50 (turn the power off and then back on) and then perform
the check again with a USB memory device other than the one with which the error first occurred.
● Do not remove and insert a USB memory device during writing to a USB memory device.
A USB memory device may not be recognized if it is removed and inserted within a short period of time.
If that happens, the unit needs to be restarted (turn the power off and then back on).