[IV Product specifications and functions]

2. AE-200/AE-50/EW-50 unit functions and Web browser functions

The following table lists the AE-200/AE-50/EW-50 unit functions and Web browser functions.
Item
ON/OFF/Test run
The equipment can be turned on and off and operated per group, per block, or per floor, or
collectively. When the test run mode is selected, the test run operation can be performed. (Unit
screen only)
Operation mode
The operation mode can be switched between Cool, Dry, Heat, Fan, and Auto per group, per block,
or per floor, or collectively.
Set temperature
The indoor temperature can be set per group, per block, or per floor, or collectively. (0.5°C (1°F)
increments)
Setting temperature range
Fan speed / Air flow
The fan speed can be switched to any of four levels per group, per block, or per floor, or collectively.
(LOSSNAY)
(There may be no levels, 2 levels, 3 levels, or 4 levels depending on the model, and auto operation is
*1
available for models with an auto function.)
(In the case of LOSSNAY, the fan speed can be switched to Very Low, Low, High, and Auto. The air
flow levels that can be selected differ depending on the model. However, there are the two levels of
Low and High in the case of an interlocked LOSSNAY.)
Air flow direction
The air direction setting can be switched to any of five vertical air flow directions, auto, and swing per
setting
group, per block, or per floor, or collectively. (The air flow functions that can be selected differ
depending on the model.)
Operation with five air flow directions and auto is possible only for the models with those functions.
Ventilation mode
The ventilation mode can be switched to any of Bypass, Heat Recovery, and Auto per group, per
(LOSSNAY)*1
block, or per floor, or collectively.
ON/OFF of interlocked
When there are interlocked LOSSNAY, they can be switched ON (high/low) or OFF per group or per
LOSSNAY*1
block, or collectively.
Monitoring of energy
The electric energy consumption, outdoor temperature, operation time, and other information can be
use status*2
displayed and compared in bar graphs and line graphs.
Note: A PI controller and electricity meter (pulse output type) need to be connected to display the
Ranking*2
The consumption and time can be displayed ranked in order of largest to smallest for electric energy
consumption and fan operation time.
Note: The ranking of electric energy consumption can only be displayed by block.
Target value settings*2
The target value for electric energy consumption can be set on an annual, monthly, or weekly basis
and by block.
The set value is displayed in the Energy Use Status screen and the Ranking screen.
Peak cut control
The peak cut control level and electric energy can be displayed.
status*2
Note: A license is required.
Air-conditioner,
The weekly schedule, annual schedule, and today's schedule for the day-of-week pattern can be set
ventilator, and general
for each group per group, per block, or per floor, or collectively.
● Up to 24 events can be scheduled for each day, and the "ON/OFF," "Operation Mode," "Set
equipment schedules
● There are five types of weekly schedule, and the season schedule settings can be set.
● The schedule events of the weekly, yearly, or today's schedule are executed on a set day, and
● With the yearly schedule, the days of national holidays and summer holidays and other days
● [Optimized Start] can be set so that the set temperature is reached at the set time. (Indoor units
Cool/Dry: 19°C to 35°C (66°F to 95°F) (14°C to 30°C (57°F to 86°F)
Heat:
Auto:
Note: The settable temperature differs depending on the model.
Note: The set temperature may be in 1°C (2°F) increments depending on the model.
Note: The set temperature may be able to be registered for each of the cool and heat
modes depending on the model.
electric energy consumption.
The electric energy consumption cannot be displayed with a PLC for Electric Amount Count
connection.
An AI controller or AHC and a temperature sensor need to be connected for outdoor
temperature display.
Temperature," "Air Direction," "Fan Speed," and "Prohibit Local Remote Controller Operation"
settings can be set.
(In the case of LOSSNAY, the "ON/OFF," "Ventilation Mode," and "Air Flow," and "Prohibit Local
Remote Controller Operation" settings can be set for schedule operation.)
the priority for execution from the highest level to lowest level is [Today] → [Yearly] → [Week 1]
→ ... → [Week 5].
that do not fit in the weekly schedule can be set on 50 days within the range up to 24 months in
the future.
Five operation patterns can be set for each group.
only)
Note: The items that can be set differ depending on the model (function) of the air conditioner.
Description
when mid temperature model connected)
4.5°C – 28°C (40°F – 82°F)
19°C to 28°C (66°F to 82°F) (17°C to 28°C (63°F to 82°F)
when mid temperature model connected)
36
○: Function available